Description
If the input is closed, following commands received via any external terminal (e.g. from InteliMonitor or from
a remote display) are inactive:
Remote engine start, stop commands
No setpoints can be adjusted
Controller mode (e.g. OFF-RUN) cannot be changed
Fault reset and horn reset commands
All other commands (e.g. change of a Remote Switch state)
It is possible to list Setpoints, Values and History
Binary input functions are without change
Engine can be started, stopped via Binary inputs (e.g.
) or via front panel
buttons.
Note:
When this Access Lock input is active, it is still possible to initiate programming from a remotely
connected DriveConfig.
Note:
If you need to lock only some of the external terminals, you can use following inputs:
Device
Command
AccessLock int
AccessLock ext
LOC (Local) mode
ID-DCU Industrial panel
START
N
Y
Y
STOP
N
Y
Y
FLT RES
Y
Y
Y
HORN
RES
Y
Y
Y
Setpoint
change
N
Y
Y
Mode
change
N
Y
Y
ID-DCU Industrial Bin Inputs
Remote
Y
Y
N
InteliDrive local/remote commands blocking overview
Note: Y = available, N = blocked
AccessLock ext
Содержание InteliDrive DCU Industrial
Страница 5: ...InteliDrive DCU Industrial 3 4 0 Global Guide 5 8 2 13 Theory of binary inputs and outputs 347...
Страница 29: ...InteliDrive DCU Industrial 3 4 0 Global Guide 29...
Страница 97: ...InteliDrive DCU Industrial 3 4 0 Global Guide 97 8 Appendix 6 back to Table of contents...
Страница 246: ...InteliDrive DCU Industrial 3 4 0 Global Guide 246 Analog inputs from J1939 configuration...
Страница 263: ...InteliDrive DCU Industrial 3 4 0 Global Guide 263 6 back to List of setpoints...
Страница 281: ...InteliDrive DCU Industrial 3 4 0 Global Guide 281 6 back to Appendix 6 back to Table of contents...
Страница 294: ...InteliDrive DCU Industrial 3 4 0 Global Guide 294 Dimensions Note Unit is 35 mm DIN rail mounted Terminals...
Страница 306: ...InteliDrive DCU Industrial 3 4 0 Global Guide 306 Dimensions Note Unit is 35 mm DIN rail mounted...
Страница 314: ...InteliDrive DCU Industrial 3 4 0 Global Guide 314 Dimensions Unit is 35 mm DIN rail mounted Terminals...
Страница 350: ...InteliDrive DCU Industrial 3 4 0 Global Guide 350 6 back to Theory of binary inputs and outputs...