InteliDrive DCU Industrial 3.4.0 Global Guide
124
Engine protect
Setpoint group
Engine protect
Related FW
3.4.0
Range [units]
0 .. 600 [s]
Default value
10
Force value
Alternative config
Step
1
Comm object
8264
Related applications
AS, SS
Description
The maximum time for which is the binary output Horn closed (horn, buzzer will sound). If it is requested to
sound hound until alarm is cleared, set the parameter to zero.
Horn Timeout
Setpoint group
Engine protect
Related FW
3.4.0
Range [units]
0 .. 60 [s]
Default value
10
Force value
Alternative config
Step
1
Comm object
10023
Related applications
AS, SS
Description
This parameter adjusts delay after engine start when alarms configured as RunOnlyBlkDel1 (i.e. "running
only", group #1) are started to be evaluated. The "running only" alarms are not beeing evaluated while the
engine is not running or then, after start, while the adjusted delay is running.
For details see drawing, which is part of
description.
RunOnlyBlkDel1
Setpoint group
Engine protect
Related FW
3.4.0
Range [units]
0 .. 60 [s]
Default value
20
Force value
Alternative config
Step
1
Comm object
10024
Related applications
AS, SS
Description
This parameter adjusts delay after engine start when alarms configured as RunOnlyBlkDel2 (i.e. "running
only", group #2) are started to be evaluated. The "running only" alarms are not beeing evaluated while the
engine is not running or then, after start, while the adjusted delay is running.
For details see drawing, which is part of
description.
RunOnlyBlkDel2
Содержание InteliDrive DCU Industrial
Страница 5: ...InteliDrive DCU Industrial 3 4 0 Global Guide 5 8 2 13 Theory of binary inputs and outputs 347...
Страница 29: ...InteliDrive DCU Industrial 3 4 0 Global Guide 29...
Страница 97: ...InteliDrive DCU Industrial 3 4 0 Global Guide 97 8 Appendix 6 back to Table of contents...
Страница 246: ...InteliDrive DCU Industrial 3 4 0 Global Guide 246 Analog inputs from J1939 configuration...
Страница 263: ...InteliDrive DCU Industrial 3 4 0 Global Guide 263 6 back to List of setpoints...
Страница 281: ...InteliDrive DCU Industrial 3 4 0 Global Guide 281 6 back to Appendix 6 back to Table of contents...
Страница 294: ...InteliDrive DCU Industrial 3 4 0 Global Guide 294 Dimensions Note Unit is 35 mm DIN rail mounted Terminals...
Страница 306: ...InteliDrive DCU Industrial 3 4 0 Global Guide 306 Dimensions Note Unit is 35 mm DIN rail mounted...
Страница 314: ...InteliDrive DCU Industrial 3 4 0 Global Guide 314 Dimensions Unit is 35 mm DIN rail mounted Terminals...
Страница 350: ...InteliDrive DCU Industrial 3 4 0 Global Guide 350 6 back to Theory of binary inputs and outputs...