IGS-NT Communication Guide
104
7.4.12 External Value1 – writing
Request:
01 10 18 D6 00 03 06 00 02 00 24 00 23 04 84
01
= controller address
10
= Modbus command
18 D6
= Register address: Object for engine commands (46359) – 40001 = 6358 DEC =>
18D6 HEX
00 03
= number of Modbus registers
06
= data length in bytes (00023)
00020024
= argument for Set ExtValue 1-4 (
) (value
36DEC = 0024HEX)
0023
= command number (
), command = 35 DEC =
0023 HEX
84 04
=
Check field calculation (page 143)
(write LSB MSB !)
Response:
01 10 18 D6 00 03 67 50
01
= Controller address
10
= Modbus command
18 D6
= Register addres
00 03
= Release value, number of written Modbus registers
50 67
=
Check field calculation (page 143)
Note:
Writing External Value in one step is possible only with direct connection to controller. If communication
bridge (IB-NT or I-LB+) is used, it is necessary to write the command and argument in two steps.
Содержание Inteli Mains NT BaseBox
Страница 12: ...IGS NT Communication Guide 12 2 1 IG IS IM NTC BB Communications...
Страница 13: ...IGS NT Communication Guide 13 2 2 IG IS IM NTC BB Terminals...
Страница 14: ...IGS NT Communication Guide 14 2 3 IG IS IM NTC BB Peripheral modules...
Страница 15: ...IGS NT Communication Guide 15 2 4 IG IS IM NTC BB Jumpers settings...
Страница 16: ...IGS NT Communication Guide 16 2 5 IG IM NT BB Communication...
Страница 17: ...IGS NT Communication Guide 17 2 6 IG IM NT BB Terminal...
Страница 18: ...IGS NT Communication Guide 18 2 7 IG IM NT BB Peripheral modules...
Страница 19: ...IGS NT Communication Guide 19 2 8 IG IM NT BB Jumper settings...
Страница 20: ...IGS NT Communication Guide 20 2 9 IG NT Communications Terminals...
Страница 22: ...IGS NT Communication Guide 22 2 11 IM NT Communications Terminals...
Страница 23: ...IGS NT Communication Guide 23 2 12 IS NT BB Communications Terminals...
Страница 65: ...IGS NT Communication Guide 65...
Страница 114: ...IGS NT Communication Guide 114 Image 7 2 InternetBridge NT wired internet connection...