It is not destined for normal operation. Please refer to the Troubleshooting
guide for more information (chapter "MGCB is not closed although gensets
are running").
N
OTE
:
# sign in the name of this setpoint marks that this setpoint is shared among
all controllers connected by CAN2 bus.
12.2.8.7
Setpoint: #LoadResStop 1
Group
Pwr Management
Range [units]
Related FW
3.0
Description
This setpoint is used to adjust the load reserve for stop in absolute mode. i.e.
= ABS (kW) or ABS (kVA) if the reserve set #1 is active.
Learn more about reserves in the chapter
Reserves, minimal running power
.
The currently active reserve set is selected by binary inputs
. If none of these inputs is active the set #1 is selected.
N
OTE
:
The reserve for stop must be always adjusted higher than the reserve for
start.
N
OTE
:
# sign in the name of this setpoint marks that this setpoint is shared among
all controllers connected by CAN2 bus.
12.2.8.8
Setpoint: #LoadResStrt 2
Group
Pwr Management
Range [units]
-32000 ..
Related FW
3.0
Description
This setpoint is used to adjust the load reserve for start in absolute mode. i.e.
= ABS (kW) or ABS (kVA) if the reserve set #2 is active.
Learn more about reserves in the chapter
Reserves, minimal running power
.
The currently active reserve set is selected by binary inputs
. If none of these inputs is active the set #1 is selected.
N
OTE
:
Содержание IM-NT
Страница 86: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 86 APPENDIX...
Страница 326: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 326 17 User Notes...
Страница 327: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 327...
Страница 328: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 328...