InteliMains
NT
, SW version 3.0
InteliMains-NT-BTB-3.0-Reference Guide.pdf,
©ComAp – June 2013
127
Range [units]
[-]
Related FW
3.0
Description
This setpoint can be used to add extra AT commands at the end of the
initialization sequence of the modem connected to the COM2 port. The
command can be entered with as well as without the "AT" prefix, are
separated with semicolon and maximal length is 31 characters.
The setpoint can't be modified via the IG-NT built-in terminal.
Using a modem at the COM2 port is not supported since the hardware
version 2.0. For modem use the COM1 port instead.
12.2.3.10
Setpoint: RS485(1) conv.
Group
Comms settings
Range [units]
DISABLED, ENABLED [-]
Related FW
3.0
Description
This setpoint selects function of the built-in RS485(1) converter.
ENABLED
The communication port COM1 is redirected to the
integrated RS485(1) converter. The RS232(1) connector
has no function and the external display interface is not
available.
DISABLED
The communication port COM1 is present at the RS232(1)
connector and the RS485(1) connector is used for the
external display interface.
N
OTE
:
The redirection is applied only for DIRECT, MODBUS and ECU-LINK modes.
See the setpoint
N
OTE
:
This setpoint must be set to
DISABLED
at controllers that do not have
internal display. i.e. InteliVision-5 or InteliVision-8 is connected to the
RS485(1) terminals.
Содержание IM-NT
Страница 86: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 86 APPENDIX...
Страница 326: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 326 17 User Notes...
Страница 327: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 327...
Страница 328: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 328...