L
OADSHARING MODE
Load ctrl PtM
= SYSBLD->LS
The system
baseload is
maintained by
the IM-NT over
the load
sharing.
N
OTE
:
# sign in the name of this setpoint marks that this setpoint is shared among
all controllers connected by CAN2 bus.
12.2.1.2
Setpoint: #SysPwrFactor
Group
Process Control
Range [units]
0.60 .. 1.20 [-]
Related FW
3.0
Description
In BTB application many load control and power management functions does
not play active role!
The setpoint is used for adjusting the requested base power factor of the
gen-sets in the parallel-to-mains operation. The setpoint
must be set to BASEPF for constant power factor control. The power factor of
each gen-set is controlled by it's own PF control loop and InteliMains does
not play active role in this type of control.
Settings 0.60
– 0.99 correspond to inductive PF (0.60L - 0.99L), 1.01 – 1.20
correspond to capacitive PF (0.99C - 0.80C).
N
OTE
:
# sign in the name of this setpoint marks that this setpoint is shared among
all controllers connected by CAN2 bus.
12.2.1.3
Setpoint: #SysLdCtrl PtM
Group
Process Control
Range
[units]
BASELOAD, LDSHARING [-]
Related
3.0
Содержание IM-NT
Страница 86: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 86 APPENDIX...
Страница 326: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 326 17 User Notes...
Страница 327: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 327...
Страница 328: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 328...