IGS-NT-BC, SW Version 1.2.0,
©ComAp – January 2019
IGS-NT-BC-1.2.0 Reference Guide.PDF
87
ENABLED
The communication port COM1 is redirected to the integrated
RS485(1) converter. The RS232(1) connector has no function
and the external display interface is not available.
DISABLED
The communication port COM1 is present at the RS232(1)
connector and the RS485(1) connector is used for the external
display interface.
N
OTE
:
The redirection is applied only for DIRECT, MODBUS and ECU-LINK modes. See
the setpoint
N
OTE
:
This setpoint must be set to
DISABLED
at controllers that do not have internal
display. i.e. InteliVision-5 or InteliVision-8 is connected to the RS485(1) terminals.
Setpoint: RS232(2)MdmIni
Group
Comms settings
Range [units]
[-]
Related FW
3.0
Description
This setpoint can be used to add extra AT commands at the end of the
initialization sequence of the modem connected to the COM2 port. The command
can be entered with as well as without the "AT" prefix, are separated with
semicolon and maximal length is 31 characters.
The setpoint can't be modified via the IG-NT built-in terminal.
Using a modem at the COM2 port is not supported since the hardware version
2.0. For modem use the COM1 port instead.
Setpoint: RS485(2) conv.
Group
Comms settings
Range [units]
DISABLED, ENABLED [-]
Related FW
3.0
Description
This setpoint selects function of the built-in RS485(2) converter.
ENABLED
The communication port COM2 is redirected to the integrated
RS485(2) converter. The RS232(2) connector has no function.
DISABLED
The communication port COM2 is present at the RS232(2)
connector.
N
OTE
:
The redirection is applied only for DIRECT, MODBUS and ECU-LINK modes. See
the setpoint
N
OTE
: