IGS-NT-BC, SW Version 1.2.0,
©ComAp – January 2019
IGS-NT-BC-1.2.0 Reference Guide.PDF
66
•
BASEPF: The gen-set power factor is controlled to a preadjusted level
•
VSHARING: The power factor is equalized with other gen-sets according
to the actual reactive load.
N
OTE
:
If the power factor control mode is switched to VSHARING the
must be switched to LDSHARING.
Setpoint: SysBaseLdMode
Group
Process control
Range [units]
INTERNAL, EXTERNAL [-]
Related FW
3.0
Force value
possible
YES
Description
This setpoint selects from where the System Base load value is taken if the load
control mode in parallel-to-mains operation is switched to baseload (i.e.
INTERNAL
The baseload is adjusted by the setpoint
EXTERNAL
The baseload is adjusted by the logical (functional) analog
input
N
OTE
:
If the external source is selected the logical analog input must be configured at
each gen-set to the identical source. The
shared peripherial modules
can be used
to distribute the value over the controllers via the CAN2 bus.
•
One controller measures the value physically on it's analog input and the
function
is configured onto this physical input. But the
value is also beeing transmitted from this controller to the CAN bus via
one shared analog output (e.g. SHAOUT #1.1).
•
The other controllers reads the value from their shared analog inputs (e.g.
SHAIN #1.1) and the function
shared inputs.
•
The transmitting controller must be always switched on!
Setpoint: SysBasePFMode
Group
Process control
Range [units]
INTERNAL, EXTERNAL [-]
Related FW
3.0
Force value
possible
YES
Description
This setpoint selects from where the System Power Factor value is taken if the PF