IGS-NT-BC, SW Version 1.2.0,
©ComAp – January 2019
IGS-NT-BC-1.2.0 Reference Guide.PDF
31
Alarm: GCB fail
BO GCB close/open
BI GCB feedback
Alarm detection:
immediatelly
active
closed
opened
Alarm: GCB fail
BI GCB feedback
BO GCB close/open
Alarm detection:
immediatelly
active
opened
closed
When the BO CB close/open opens, there is 5 resp. 2 sec delay for the breaker to respond before a CB
fail is detected. In such case, if CB OFF coil is used for opening the CB and CB fail occurs during
opening the CB, the signal CB OFF coil is automatically extended until the breaker opening is detected
(evaluated as CB status).
•
2 sec when the CB is used for synchronizing
•
5 sec in other cases
Alarm: GCB fail
BO GCB close/open
BI GCB feedback
active
opened
opened
Time delay
5 sec
In case that CB fail is detected after switching the controller on (CB is closed), the CB OFF coil output is
activated immediatelly.
Remote Alarm Messaging
It is possible to use up to five channels for Active Call, Email and SMS upon defined type of Alarm. It is
possible to define protection type for all ENABLED channels to react. All the possibilities in the controller are:
History record, Alarm only, Warning, Mains protect and Mains protect with Reset. Find more information
about alarm types in the chapter Protections and alarm management.
Communication Types for Remote Alarm Messaging
Below there all types of communication available for each Active Call channel.
DATA-ANA
: This option sends a complete archive to the recipient's PC via analog modem. An analog
modem must be connected either to one of controller COM ports or to one of I-LB modules connected to the
controller via CAN2 bus. The channel address must contain complete telephone number of the recipient's
PC where InteliMonitor is running in Active call receiving mode.
DATA-GSM:
This option sends a complete archive to the recipient's PC via GSM modem. A GSM modem
with activated CSD data transfers must be connected either to one of controller COM ports or to one of I-LB
modules connected to the controller via CAN2 bus. The channel address must contain complete telephone
number of the recipient's PC where InteliMonitor is running in Active call receiving mode.
DATA-ISDN:
This option sends a complete archive to the recipient's PC via ISDN modem. An ISDN modem
must be connected either to one of controller COM ports or to one of I-LB modules connected to the
controller via CAN2 bus. The channel address must contain complete telephone number of the recipient's
PC where InteliMonitor is running in Active call receiving mode.
DATA-CDMA:
This option sends a complete archive to the recipient's PC via CDMA modem. A CDMA
modem must be connected either to one of controller COM ports or to one of I-LB modules connected to the
controller via CAN2 bus. The local CDMA network must allow point-to-point data transfers. The channel
address must contain complete telephone number of the recipient's PC where InteliMonitor is running in
Active call receiving mode.
SMS-GSM:
This option sends a short text message (SMS) containing the actual Alarmlist contents to the
recipient's mobile phone via the GSM modem. The channel address must contain complete telephone
number of the recipient's mobile phone.