IGS-NT-BC, SW Version 1.2.0,
©ComAp – January 2019
IGS-NT-BC-1.2.0 Reference Guide.PDF
125
i.e. the speed governor output is reset to default value and then frequency
regulation loop is started again. If NO TIMEOUT is selected the automatic restart
occurs every 180s. This method helps to sychronize successfully even in difficult
conditions.
Group: Volt/PF ctrl
Setpoint: Voltage gain
Group
Volt/PF Ctrl
Range [units]
0.0 .. 200.0 [%]
Related FW
3.0
Description
This setpoint adjusts the gain factor (P-factor) of the voltage control PI loop. The
integration factor (I-factor) for the voltage control loop is adjusted by the setpoint
N
OTE
:
See the chapter
Regulation loops overview
for general information about
regulation loops and their adjustment.
Setpoint: Voltage Int
Group
Volt/PF Ctrl
Range [units]
0 .. 100 [%]
Related FW
3.0
Description
This setpoint adjusts the relative integration factor (I-factor) of the voltage control
PI loop. The gain factor (P-factor) for the voltage control loop is adjusted by the
setpoint
Group: Force value
Setpoint: Force value 1
Group
Force value
Range [units]
[-]
Related FW
3.0
Description
This is one of the 16 setpoints reserved for using as alternative setpoints for the
force value functions. The alternative setpoint is to be assigned to a particular
force value function and renamed in GenConfig.
See also the input
N
OTE
:
It is not obligatory to use one of these reserved setpoints for a force value
function. It is possible to use also any other setpoint or value with matching
dimension and decimal resolution.
N
OTE
: