Accessory Modules for IL-NT, IC-NT, IA-NT and ID-Lite Global Guide
44
4.10.4 Others information
Setpoint group
LiteEdit configuration
Range [units]
-32 000 – 32 000 l
Default value
0
Force value
Alternative config
YES
Step
1 l
Comm object
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Actually refilled amount of fuel in liters. After editing this setpoint, its value is added to the actual value of
counter FuelManRefTot in values group Fuel Mgmt and immediatelly reset to 0.
Note:
Editation window of this setpoint is automatically entered after holding the button
Refil
on the
unit panel for minimum 1 s.
FuelManRefil [l]
Setpoint group
LiteEdit configuration
Range [units]
1 – 9999 ppl
Default value
1
Force value
Alternative config
YES
Step
1 ppl
Comm object
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
“Pulses per liter” constant of fuel flow sensor connected to the first pulse input of IL-NT-FCM module. By
setting this constant, the propper counting of FuelConH value in values group Fuel Mgmt is provided,
showing the hourly fuel consumption.
ConPulseRate [ppl]
Setpoint group
LiteEdit configuration
Range [units]
1 – 9999 ppl
Default value
1
Force value
Alternative config
YES
Step
1 ppl
Comm object
Related applications
AMF, MRS
Config level
Standard
AuRefPulseRate [ppl]