ECON-4 1.4.0 Global Guide
69
8.1.6 Act type 1 – predefined for Woodward ITB 0-200 mA
There are 4 identical groups of setpoints in ECON-4. They are used to setup the output circuits for particular
types of actuators and tune the actuator position PID loop.
Note:
Normally these Actuator type setpoints are predefined from the factory and there is no need to readjust
them. Modify them if you have a non-standard, or non listed actuator only –
see List of tested actuators by
Setpoint group
ActType 1,2,3,4
Related FW
1.4.0
Range [units]
0.0 – 1000.0 [%]
Default value
50%
Force value
NO
Step
0.1 %
Comm object
11109
Related applications
ALL
Setpoint visibility
WinScope only
Description
Gain of the PID actuator position control loop.
Act gain
Setpoint group
ActType 1,2,3,4
Related FW
1.4.0
Range [units]
0 – 1000 [%]
Default value
20%
Force value
NO
Step
1 %
Comm object
11110
Related applications
ALL
Setpoint visibility
WinScope only
Description
Integration factor of the PID actuator position control loop.
Act int
Setpoint group
ActType 1,2,3,4
Related FW
1.4.0
configured ECON-4 extension
module
Range [units]
0 – 1000 %
Default value
0%
Force value
NO
Step
1 %
Comm object
11111
Related applications
ALL
Setpoint visibility
WinScope only
Description
Derivation factor of the PID actuator position control loop.
Act der