ECON-4 1.4.0 Global Guide
62
Setpoint group
Main PID
Related FW
1.4.0
configured ECON-4
ADV extension module
Range [units]
0 – 100.0 %
Default value
80%
Force value
NO
Step
0.1 %
Comm object
13982
Related applications
ALL
Setpoint visibility
WinScope only
Description
There is 5 load bands defined via setpoints
Load 1
to
Load 5
and different
Load gain
,
Load Int
,
Load der
and
Load anticip
setpoints are active in each band.
Load 4
Setpoint group
Main PID
Related FW
1.4.0
configured ECON-4 extension
module
Range [units]
0.0 - 100.0 [%]
Default value
0%
Force value
NO
Step
0.1 %
Comm object
7182
Related applications
ALL
Setpoint visibility
Always
Description
Droop of speed governor. The governor lovers the speed reference by
Droop
percent of the
over the range from zero to
.
Droop