ECON-4 1.4.0 Global Guide
63
Setpoint group
Main PID
Related FW
1.4.0
configured ECON-4 extension
module
Range [units]
0.0 – 100.0 %
Default value
100%
Force value
NO
Step
0.1 %
Comm object
7184
Related applications
ALL
Setpoint visibility
Always
Description
Maximum output from the PID speed control loop + Load anticipation signal. It limits the maximum fuel
delivered to the engine.
MaxFuel
Note:
It is also used as coordinate for Speed/Fuel line. See description in chapter Speed governor function in
parallel mode.
Setpoint group
Main PID
Related FW
1.4.0
configured ECON-4 extension
module
Range [units]
0.0 – 100.0 %
Default value
10%
Force value
NO
Step
0.1 %
Comm object
7192
Related applications
ALL
Setpoint visibility
Always
Description
IdleFuel is base (together with MaxFuel) for Droop function calculation..
IdleFuel
Note:
Set this setpoint after engine is running on Nominal speed (no load) according to the real position of
Actuator lever