CRN2 EM Battery Instruction Manual
EMERGENCY LED DRIVER
30W/40W/60W
currentlighting.com/columbialighting
© 2022 HLI Solutions, Inc. All rights reserved. Information and specifications subject to change
without notice. All values are design or typical values when measured under laboratory conditions.
Page 1 of 5
Rev 01/06/23
COL_CRN2_LSCS EM Battery_inst_R01
CAUTION
RISK OF SHOCK-Disconnect emergency and normal input power sources before servicing.
Assembly and Field Installation Wiring: Warning
AC power must be off before proceeding with assembly or installation of emergency driver.
IMPORTANT:
An unswitched AC power source is required (100-347 VAC, 50/60 Hz).
This device is designed for fixtures listed for dry, damp or wet locations.
IMPORTANT:
Customers are advised to charge emergency LED driver 24 hours every 6 months during storage
IMPORTANT:
For BLD-RM30X-YYY suggested to use for LED lamp less than 200W(when diming to minimum.
The power needs to be less than 25W).
For BLD-RM40X-YYY suggested to use for LED lamp less than 300W (when dimming to minimum the power needs to be less than 35W)
IMPORTANT:
Make sure all connections are in accordance with the National Electrical Code or Canadian Electrical Code and any local regulations.
CAUTION:
To reduce the risk of electric shock disconnect both normal and emergency sources within this unit before servicing any equipment
connected to this unit.
CAUTION:
Do not mount near gas or electric heaters
CAUTION:
Equipment should be mounted in locations and at heights where it will not be subjected to tampering by unauthorized personnel.
CAUTION:
The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
CAUTION:
Do not use this equipment for other than its intended use
CAUTION:
Use with grounded, UL Listed, dry or damp location rated fixtures. Case should also be grounded.
CAUTION:
This product is for use in indoor fixtures only. Do NOT use near heated air handling outlets or hazardous locations
CAUTION:
Battery is rechargeable Li-ion type and must be recycled or disposed of properly.
Do not use this emergency driver with accessory equipment other than recommended by the manufacturer.
Failure to follow this may cuase an unsafe condition and will void warranty.
Servicing of this equipment should be performed by qualified personnel only.
IMPORTANT: Illuminated Indicator (LED light) means battery is in charge mode when AC power is applied.
It is recommended and required by
applicable code to test emergency function to ensure proper operation of the system; press the remote controller ON button every 30 days to
ensure the emergency driver is functioning and LED light source is illuminated. Conduct a ninety minute (90) discharge test one time (1) per year;
LED light source should be illuminated for a minimum of ninety minutes (90).
TESTING SYSTEM:
The emergency battery requires a minimum charge of one (1) hour before testing the circuit.
A full charge requires twenty four (24) hours.
FEATURES
• Simple wiring: directly connect to LED driver AC input
• Constant power output 30W/40W/60W
• Universal input range, 100-347VAC, 50/60HZ
• High output voltage DC 170V
• Optimized design for UFO highbay, private mold patent design
• Built-in integrated junction box
• Protection: over-voltage, short circuit, over-load, open-circuit
• Wireless remote control or non-remote control for emergency test
are optional
• UL Listed for field factory installation
• Comply with UL924 standard and CSA 22.2, No. 141 for USA and
Canada.
• California Energy Commission (CEC) Title 20 with BC compliant
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be followed including the following.
PLEASE READ AND FOLLOW ALL SAFETY INSTRUCTIONS
Li-ion
THIS PRODUCT CONTAINS A RECHARGEABLE LITHIUM BATTERY.
THE BATTERY MUST BE RECYCLED OR DISPOSED OFF
PROPERLY.
E 493915
Model NO.
Model Number
Input Voltage
Emergency Power
Emergency Time
BLD-RM30XY-YY
100-347VAC
30
90 Minutes
BLD-RM40XY-YY
100-347VAC
40
90 Minutes
BLD-RM60XY-YY
100-347VAC
60
90 Minutes
Specifications
Input Voltage 100-347VAC 50/60 Hz
Test switch/charging
indicator light
☐ Remote Control
☐ Non-Remote Control
Output Voltage 170V DC
Battery Li-ion battery
Input Current ≥ 200mA
Charging Time ≥ 24 hours
Input Power 15W
Output Power ☐ 30W ☐ 40W ☐60W
Emergency Time 90 minutes
Warranty 5 Years
Weight 3.3 kg
Ambient Temp. 5°C-50°C
Dimensions 273.26 x � 142.3mm