background image

15

Since the expansion tank acts as a reference point for the

pump, there cannot be two reference points (two expansion
tanks) in a system (unless manifolded together). If system
volume or other design considerations warrant the placement
of another expansion tank somewhere in the system, the expan-
sion tank in the 30RA hydronic package MUST be disconnect-
ed from its hose and the end of the hose securely plugged.

This is also true for applications where two or more 30RA

chillers are placed in parallel. There should not be more than
one expansion tank in the system (unless manifolded together
as seen in Fig. 12). The expansion tanks must be disconnected
from the 30RA hydronic package. It is permissible to install the
expansion tank(s) in a portion of the return water line that is
common to all pumps, providing that the tank is properly sized
for combined system volume.

If the application involves two or more chillers in a primary-

secondary system, a common place for mounting the
expansion tank is in the chilled water return line, just before the
decoupler. See Fig. 12 for placement of expansion tank in
primary-secondary systems.

The expansion tank included in the 30RA hydronic package

is a diaphragm tank, meaning that a flexible diaphragm physi-
cally separates the water/air interface. With this type of expan-
sion tank, it is undesirable to have any air in the water loop. See
the section on air separation on page 13 for instructions on
providing air separation equipment.
FILLING THE SYSTEM — The  initial  fill  of  the  chilled
water system must accomplish three purposes:

1. The entire piping system must be filled with water.
2. The pressure at the top of the system must be high enough

to vent air from the system (usually 4 psig is adequate for
most vents).

3. The pressure at all points in the system must be high

enough to prevent flashing in the piping or cavitation in
the pump.

The pressure created by an operating pump affects system

pressure at all points except one — the connection of the
compression tank to the system. This is the only location in the
system where pump operation will not give erroneous pressure
indications during the fill. Therefore, the best location to install
the fill connection is close to the expansion tank. An air vent
should be installed close by to help eliminate air that enters
during the fill procedure.
Ensure the following when filling the system:

1. Remove temporary bypass piping and cleaning/flushing

equipment.

2. Check to make sure all drain plugs are installed.

3. Open the blow-down valve to flush the strainer.

Normally, a closed system needs to be filled only once. The

actual filling process is generally a fairly simple procedure. All
air should be purged or vented from the system. Thorough
venting at the high points and circulation at room temperature
for several hours is recommended.
NOTE:  Local codes concerning backflow devices and other
protection of the city water system should be consulted and
followed to prevent contamination of the public water
supply. This is especially important when anti-freeze is used
in the system.
Set Water Flow Rate — Once the system is cleaned, pressur-
ized, and filled, the flow rate through the chiller needs to be
established. On units with the hydronic package, this can best
be done using the balancing valve. 

In order to adjust the balancing valve, put a differential

pressure gage across the pressure taps on the valve. Make sure
that all system isolation and control valves are open. Use
Tables 4 and 5 or a Bell & Gossett balancing valve calculator to
determine GPM. To read Tables 4 and 5:

1. Measure the pressure drop across the balancing valve. If

the pressure reading is in psi, multiply psi x 2.31 to con-
vert to feet of water before using Tables 4 and 5.

2. Go to the row in the chart corresponding to the setting on

the valve, interpolating if necessary.

3. The GPM corresponding to the pressure drop measured is

the flow through the balancing valve. 

NOTE: Colortronic recommends a differential pressure gage when
measuring pressures across the pumps or balancing valves.
This provides for greater accuracy and reduces error build-up
that often occurs when subtracting pressures made by different
gages.

On primary/secondary systems, it is advisable to set the

30RA balancing valve to maintain design flow plus 10%
through the chiller.

A rough estimate of water flow can also be obtained from

the pressure gages across the 30RA heat exchanger.
Figures 15A-16B show the relationship between GPM and
heat exchanger pressure drop. It should be noted that these
curves are for “clean” heat exchangers; they do not apply to
heat exchangers with fouling. To read the chart, subtract the
readings of the two pressure gages on the hydronic kit. This
number is the pressure drop across the heat exchanger. Adjust
the factory-installed balancing valve or external balancing
valve (units without hydronic package) until the correct pres-
sure drop is obtained for the required GPM.

Table 4 — Head (Ft Water) as Read on Balancing Valve for 30RA010-030

Table 5 — Head (Ft Water) as Read on Balancing Valve for 30RA032-055

SETTING

GPM

0

5

10

15

20

25

30

35

40

45

50

55

60

65

70

75

80

85

90

95

100

0

0

0

0.1

0.3

0.6

0.9

1.3

1.8

2.3

2.9

3.6

4.4

5.2

6.1

7.1

8.1

9.2

10.4

11.7

13

14.4

10

0

0.1

0.3

0.7

1.2

1.8

2.7

3.6

4.7

6

7.4

8.9

10.6

12.4

14.4

16.6

18.9

20

0

0.2

0.7

1.6

2.9

4.6

6.6

8.9

11.7

14.8

18.2

30

0

0.5

2

4.6

8.1

12.7

18.3

40

0

1.6

6.2

14

50

0

4.1

16.2

SETTING

GPM

40

50

60

70

80

85

90

95

100

105

110

115

120

125

130

135

140

0

0.9

1.4

2

2.7

3.5

4

4.4

4.9

5.5

6

6.6

7.2

7.9

8.5

9.2

10

10.7

10

1.6

2.5

3.6

5

6.5

7.3

8.2

9.1

10.1

11.2

12.3

13.4

14.6

15.8

17.1

18.5

19.9

20

3.4

5.3

7.6

10.4

13.6

15.3

17.2

19.1

21.2

23.4

25.7

28.1

30.5

33.1

35.8

38.7

41.6

30

8.5

13.3

19.2

26.2

34.2

38.6

43.2

48.2

53.4

58.9

64.6

70.6

76.9

83.4

90.2

97.3

104.7

40

23.7

37

53.2

72.4

94.6

106.8

119.8

133.4

147.8

163

178.9

195.5

212.9

231

249.8

269.4

289.8

50

54.6

85.3

122.8

167.2

218.3

246.5

276.3

307.9

341.1

376.1

412.8

451.1

491.2

533

576.5

621.7

668.6

Содержание AquaSnap 30RAN010-055

Страница 1: ...ure and on tags stickers and labels attached to the equipment Follow all safety codes Wear safety glasses and work gloves Keep quenching cloth and fire extinguisher nearby when brazing Use care in han...

Страница 2: ...8 018 110 146 203 194 653 018 117 161 218 215 711 022 174 237 198 186 795 022 187 268 215 211 881 025 181 241 204 198 824 025 194 272 221 224 911 030 193 268 210 207 878 030 208 308 224 241 981 035 37...

Страница 3: ...i freeze in cooler to prevent freezing of residual water 4 At the beginning of the next cooling season refill cooler and add recommended inhibitor Fig 3 Unit Rigging Label Detail C Copper Finned Conde...

Страница 4: ...sq ft 23 23 23 32 32 40 55 55 64 64 80 HYDRONIC MODULE Optional Pump s Strainer W Blowdown Valve Expansion Tank Pressure Gages Drain and Vent Plugs Flow Switch and Balance Valve Pump Single or Dual C...

Страница 5: ...2 97 2 97 3 72 5 11 5 11 5 95 5 95 7 43 HYDRONIC MODULE Optional Pump s Strainer W Blowdown Valve Expansion Tank Pressure Gages Drain and Vent Plugs Flow Switch and Balance Valve Pump Single or Dual C...

Страница 6: ...olid surface side Ends 3 ft 914 mm from solid surface for service access 2 Coil side clearance with accessory hail guard installed is 3 ft 914 mm to outside edge of hail guard top panel 3 Coil side cl...

Страница 7: ...id surface side Ends 3 ft 914 mm from solid surface for service access 2 Coil side clearance with accessory hail guard installed is 3 ft 914 mm to outside edge of hail guard top panel 3 Coil side clea...

Страница 8: ...surface side Ends 3 ft 914 mm from solid surface for service access 2 Coil side clearance with accessory hail guard installed is 3 ft 914 mm to out side edge of hail guard top panel 3 Coil side clear...

Страница 9: ...id surface side Ends 3 ft 914 mm from solid surface for service access 2 Coil side clearance with accessory hail guard installed is 3 ft 914 mm to outside edge of hail guard top panel 3 Coil side clea...

Страница 10: ...lid surface side Ends 3 ft 914 mm from solid surface for service access 2 Coil side clearance with accessory hail guard installed is 3 ft 914 mm to outside edge of hail guard top panel 3 Coil side cle...

Страница 11: ...d surface side Ends 3 ft 914 mm from solid surface for service access 2 Coil side clearance with accessory hail guard installed is 3 ft 914 mm to outside edge of hail guard top panel 3 Coil side clear...

Страница 12: ...hould follow sound engineer ing practice as well as applicable local and industry standards Improperly designed or installed systems may cause unsatis factory operation and or system failure Consult a...

Страница 13: ...l a temporary bypass around the chiller to avoid cir culating dirty water and particulates into the pump pack age and chiller during the flush Use a temporary circulat ing pump during the cleaning pro...

Страница 14: ...pressure drop between the tank and the pump must be accounted for NOTE If the system requires a pre charge greater than 40 psig increase pressure as described below Expansion Tank Pre Charge To pre c...

Страница 15: ...of the city water system should be consulted and followed to prevent contamination of the public water supply This is especially important when anti freeze is used in the system Set Water Flow Rate O...

Страница 16: ...available from the factory as an accessory These tanks are designed to physically fit beneath the corresponding 30RA unit taking up the same footprint Available volumes are as follows 30RA010 018 110...

Страница 17: ...where ambient tempera tures are expected to fall below 32 F Consult local water treat ment specialist on characteristics of the system water and add a recommended inhibitor to the chilled water 1 If t...

Страница 18: ...agement Module Used for any of the following types of temperature reset demand limit and ice features 4 to 20 mA leaving fluid temperature reset requires field supplied 4 to 20 mA generator 4 to 20 mA...

Страница 19: ...2 2 125 311 3 110 96 2 125 110 97 4 125 110 97 4 125 110 99 6 125 110 208 230 60 187 253 1 102 4 125 316 4 125 106 8 125 125 108 2 125 125 108 2 125 125 110 6 150 125 460 60 414 506 1 50 3 70 160 0 60...

Страница 20: ...0 2 1 9 1 3 0 380 60 2 2 9 1 4 6 042 380 415 50 2 2 3 2 2 3 230 50 2 3 8 2 3 8 045 230 60 2 4 8 2 4 8 208 230 60 2 5 3 2 5 3 460 60 2 2 4 2 2 4 575 60 2 1 9 2 1 9 380 60 2 2 9 2 2 9 380 415 50 2 2 3 2...

Страница 21: ...205 34 1 225 41 6 310 035 230 60 29 4 265 36 7 265 43 8 380 208 230 60 32 7 265 40 8 265 48 7 380 460 60 14 6 120 20 2 135 23 8 175 575 60 12 2 80 16 6 120 18 9 140 380 60 18 9 155 26 4 170 30 1 235...

Страница 22: ...move the orange harness wire from TB5 1 and wire contacts in series as shown The contacts must be rated for dry circuit application capable of handling a 24 vac load up to 50 mA 5 Terminals 11 and 13...

Страница 23: ...nge harness wire from TB5 1 and wire contacts in series as shown The contacts must be rated for dry cir cuit application capable of handling a 24 vac load up to 50 mA 5 Terminals 11 and 13 of TB5 are...

Страница 24: ...s 6 and 7 for details Do not use compressor to evacuate system REFRIGERANT CHARGE Refer to Tables 1A 1D Immediately ahead of filter drier in each circuit is a factory installed liquid line service val...

Страница 25: ...PUMP UNITS 30RA032 055 PRESSURE DROP SINGLE PUMP UNITS 30RA010 030 PRESSURE DROP SINGLE PUMP UNITS 30RA010 030 LEGEND 1 30RA010 3 30RA018 5 30RA025 7 30RA032 30RA035 9 30RA042 30RA045 11 30RA055 2 30R...

Страница 26: ...DUAL PUMP UNITS SIZES 30RA032 055 PRESSURE DROP SINGLE PUMP UNITS 30RA032 055 PRESSURE DROP SINGLE PUMP UNITS 30RA032 055 LEGEND 1 30RA010 3 30RA018 5 30RA025 7 30RA032 30RA035 9 30RA042 30RA045 11 30...

Страница 27: ...Accessory Storage Tanks 1 ACCESSORY TANK FLOW RATE gpm PRESSURE DROP ft wg 30RA 900 010 30RA 900 001 009 100 0 10 0 1 0 0 1 10 100 1000 0 1 1 0 10 0 1 0 10 0 ACCESSORY TANK FLOW RATE L s PRESSURE DROP...

Страница 28: ...scontinue or change at any time specifications or designs without notice and without incurring obligations PC 903 Catalog No 533 00045 Printed in U S A Form 30RA 12SI Pg 28 7 02 Replaces 30RA 1SI Book...

Отзывы: