Coleman P*DHX12F0801 Скачать руководство пользователя страница 7

The furnace switch (service switch) should be clearly marked,
installed in an easily accessible area between the furnace and
furnace room entry, and be located in such a manner to reduce
the likelihood that it would be mistaken as a light switch or simi-
lar device.

Accessories requiring 120 VAC power sources such as elec-
tronic air cleaners and humidifier transformers may be pow-
ered from the furnace circuit, but should have their own
controls

Do not use the direct drive motor connections as a power
source, since there is a high risk of damaging the accessories
by exposure to high voltage from the auto--generating wind-
ings of the direct drive motor.

Thermostat wiring connections and air conditioning contactor
low voltage connections are shown in the wiring diagrams on
Page 12. Some micro--electronic thermostats require addi-
tional controls and wiring. Refer to the thermostat manufac-
turer's instructions.

CAUTION: A room thermostat with independent
heat/cool circuit is required.

The thermostat should be located approximately 5 feet above
the floor, on an inside wall where there is good natural air circu-
lation, and where the thermostat will be exposed to average room
temperatures. Avoid locations where the thermostat will be ex-
posed to cold drafts, heat from nearby lamps and appliances, ex-
posure to sunlight, heat from inside wall stacks, etc.

NOTE: Some electronic thermostats do not have ad-
justable heat anticipators. They may have other type
cycle rate adjustments. Follow the thermostat manu-
facturer's instructions.

HUMIDIFIER

A humidifier is an optional accessory available through most
heating supplies outlets. Installation should be carried out in
accordance with the humidifier manufacturer's installation in-
structions. Water or water droplets from the humidifier should
not be allowed to come into contact with the furnace heat ex-
changer. Do not use direct drive motor connections as a source
of power for 120 VAC humidifiers and humidifier transformers.

PIPING INSTALLATION

The entire fuel system should be installed in accordance with
the requirements of ANSI NFPA No. 31 in the United States or
CAN/CSA B--139 in Canada, and local regulations. Use only
an approved fuel oil tanks piping, fittings and oil filter.

Ensure that all fittings used in a copper oil line system are high
quality flare fittings. Do not use compression fittings.

Pressurized or gravity feed installations must not exceed 10
PSIG on the inlet line or the return line at the pump. A pressure
greater then 10 PSIG may cause damage to the shaft seal.

The furnace may be installed with a one pipe system or gravity
feed or lift. The maximum allowable lift on a single line system is
8 ft. Lift should be measured from the bottom (outlet) of the tank
to the inlet of the burner.

Sizing a single line system is complex because of the difficulty
estimating the pressure drop through each fitting, bend and

component in the line. In general, keep single line systems
short as possible. If the furnace is to be installed in a sus-
pended position, a two pipe system may be a better alternative.

Two--stage oil pumps may be used with both single line and
two line systems. Two--stage pumps are available from your
HVAC wholesaler. Table 3 lists allowable line lengths (horizon-
tal plus vertical) for single and two stage oil pumps.

In retrofit applications where an existing oil line system is in
place, a vacuum check will help determine if a two--stage oil
pump is necessary. The vacuum in a system using a single
stage oil pump should not exceed 6" Hg. The vacuum in a sys-
tem using a two--stage oil pump should not exceed 15" Hg. For
additional information, refer to the instruction information sheet
affixed to the oil burner.

Install the oil filter as close to the burner as possible. For further
details of the oil supply tank and piping requirements, please
refer to the instructions and illustrations in the oil burner and oil
pump instructions shipped with the furnace.

OIL FILTER

All fuel systems should include an oil filter between the fuel oil
storage tank and the oil burner. When using an oil burner noz-
zle smaller than 0.65 U.S. Gallons Per Hour, install an addi-
tional 7 to 10 micron filter as close as possible to the oil burner.

OIL BURNER NOZZLES

These furnaces are certified for multiple firing rates, ranging
from 60,000 to 181,000 Btu/h depending on model. By manipu-
lating the oil burner nozzle, flame retention head, static plate
and temperature rise, the furnace may be fired at an ideal rate
for a wide range of structures. Refer to Table 4, and the furnace
rating plate to determine the proper combinations.

CAUTION: Before operating the furnace check
burner alignment with the combustion chamber. The
end cone of the air tube must be centered to the ac-
commodating ring provided in the design of the com-
bustion chamber. Adjust as necessary.

Unitary Products Group

7

035-14289-000 Rev. A (0701)

SINGLE STAGE

2-STAGE

LIFT

3/8" O.D.

TUBING

1/2" O.D.

TUBING

3/8" O.D.

TUBING

1/2" O.D.

TUBING

1

53

100

68

100

2

49

100

65

100

3

45

100

63

100

4

41

100

60

100

5

37

100

58

100

6

33

100

55

100

7

29

100

53

100

8

25

99

50

100

9

21

83

48

100

10

17

68

45

100

12

13

52

42

100

12

37

100

14

32

100

16

27

100

18

22

88

TABLE 3 - OIL PIPING LENGTHS (FEET)

Set the heat anticipator in the room thermostat to .4
amps. for models P*HBX12F080, P*DHX12F080 &
P*DHX16F120; for other models set heat anticipator at
.2 amps. Setting it lower will cause short cycles. Setting
it higher will cause the room temperature to exceed the
setpoint.

Содержание P*DHX12F0801

Страница 1: ...ency or the oil supplier P HB UPFLOW INSTALLATION INSTRUCTION OIL FIRED WARM AIR FURNACES Supersedes 035 14289 000 A 300 035 14289 000 A 1101 CAUTION THIS PRODUCT MUST BE INSTALLED IN STRICT COM PLIANCE WITH THE ENCLOSED INSTALLATION IN STRUCTIONS AND ANY APPLICABLE LOCAL STATE AND NATIONAL CODES INCLUDING BUT NOT LIM ITED TO BUILDING ELECTRICAL AND ME CHANICAL CODES WARNING IMPROPER INSTALLATION ...

Страница 2: ...ns provided the results obtained are in substantial agreement with and not less than those obtained using the procedure described in the manual LOCATION OF UNIT The furnace should be located such that the flue connection to the chimney is short direct and consists of as few elbows as possible When possible the unit should be centralized with re spect to the supply and return air duct work A centra...

Страница 3: ...6F12001 are factory shipped for downflow installation Downflow If the furnace is to be installed in a downflow application a com bustible floor base must be used either 1CB0312 or 1CB0316 Refer to Figure 1 Horizontal For applying the furnace in a horizontal left or horizontal right application follow these steps 1 Rotate the furnace 90 degrees to the desired position 2 Remove three nuts and washer...

Страница 4: ...SUPPLY AIR RETURN AIR P DHX12F08001 51 22 31 1 4 19 19 18 18 5 P DHX16F12001 62 22 1 4 22 1 4 20 1 2 20 1 2 18 18 6 LOWBOY SUPPLY AIR RETURN AIR P LBX12F08001 31 22 43 20 1 2 18 5 8 20 1 2 18 5 8 5 REAR P LBX16F12001 41 22 52 1 2 20 1 2 18 5 8 20 1 2 18 5 8 6 REAR P LBX16F14501 41 22 52 1 2 20 1 2 18 5 8 20 1 2 18 5 8 6 REAR P LBX20F19001 56 26 49 24 22 24 22 7 REAR TABLE 2 UNIT DIMENSIONS C E K H...

Страница 5: ... 2 1 2 3 1200 P DHX16F12001 140 120 1 0 80 1 1593 12 0 15 14 11 x 10 1 2 1 20 x 20 3 3 1 2 4 1600 LOWBOY P LBX12F08001 91 80 65 85 1 1717 12 0 15 14 12 x 9 1 2 1 20 x 20 2 2 1 2 3 3 1 2 4 1200 P LBX16F12001 140 120 1 0 83 4 1585 12 0 15 14 12 x12 1 2 1 20 x 25 3 3 1 2 4 1600 P LBX16F14501 168 145 1 20 83 5 1585 12 0 15 14 12 x 12 1 2 1 20 x 25 3 3 1 2 4 1600 P LBX20F19001 231 190 1 65 78 0 2135 12...

Страница 6: ...emperature sensitive fan switch is actuated by a helical bi metal sensing element enclosed in a metal guard and controls the circulating air blower This provides a delay between the burner ignition and blower start up to eliminate ex cessive flow of cold air when the blower comes on Blower shutdown is also delayed to remove any residual heat from the heat exchanger and improve the annual efficienc...

Страница 7: ...e lift on a single line system is 8 ft Lift should be measured from the bottom outlet of the tank to the inlet of the burner Sizing a single line system is complex because of the difficulty estimating the pressure drop through each fitting bend and component in the line In general keep single line systems short as possible If the furnace is to be installed in a sus pended position a two pipe syste...

Страница 8: ... amping of the direct drive blower motor Selecting a lower blower speed may cor rect this problem Direct drive blower speeds are adjusted by changing the hot wires to the motor winding connections Please refer to wiring diagram on Page 12 or the wiring diagram label affixed to the furnace THE NEUTRAL WIRE normally the white wire IS NEVER MOVED TO ADJUST THE BLOWER SPEED It is possible and acceptab...

Страница 9: ...nd debris with a wire han dled brush and an industrial vacuum cleaner Before replacing the clean out covers inspect the gaskets If the gaskets are broken remove the remnants and replace with new gaskets Snug the cleanout covers DO NOT OVER TORQUE THE CLEAN OUT NUTS Replace the inner front panel clean out covers NOTE A radiator clean out assembly inadvertently dropped into the interior of the furna...

Страница 10: ...URNER SET UP The burner air supply is adjusted to maintain the fuel to air ratio to obtain ideal combustion conditions Alack of air causes soft and sooty flames resulting in soot build up throughout the heat exchanger passages Excess combustion air causes a bright roaring fire and high stack temperatures resulting in poor fuel efficiency Preparations Drill a 1 4 test port in the venting ideally at...

Страница 11: ...e flue gases are above the range the blower may require speeding up Stack temperature varies directly with the system temperature rise System temperature rise is the difference between the furnace outlet temperature and the furnace inlet temperature as measured in the vicinity of the connection between the plenum take offs and the trunk ducts Typical temperature rise values range between 65 F and ...

Страница 12: ...H 1752 1691 1659 1593 1525 MED HIGH 1454 1454 1417 1379 1300 MED LOW 975 944 912 879 844 LOW 631 593 552 515 486 P LBX12F08001 HIGH 1917 1885 1820 1717 1608 MED HIGH 1590 1608 1590 1532 1430 MED LOW 1096 1096 1096 1068 1039 LOW 696 647 692 647 598 P LBX16F12001 P LBX16F14501 HIGH 1810 1740 1675 1585 1480 MED HIGH 1570 1540 1495 1445 1348 MED LOW 1090 1080 1070 1065 1036 LOW 710 700 690 665 614 P L...

Страница 13: ...Unitary Products Group 13 035 14289 000 Rev A 0701 WIRING DIAGRAM ALL MODELS ...

Страница 14: ...f necessary Ensure that erratic pressure readings are not caused by defective fuel oil lines Air getting into fuel oil lines or fuel oil line dirty clogged or in some manner defective Check oil lines Replace any compression fittings found with high quality flared fittings Check for any signs of oil leaks An oil leak is a potential source of air or contaminants Defective burner motor Check burner m...

Страница 15: ...ure Adjust the oil burner combustion air band and draft regulator to gain the highest CO2 possible with a Bacharach No 1 smoke Heat exchanger partially clogged Check for soot build up in heat exchanger flue passages especially in the outer radiator Furnace will not warm home to desired tempera ture Air flow blocked by dirty air filter Clean or replace air filter Thermostat adjustments or location ...

Страница 16: ...nge without notice Printed in U S A Copyright by Unitary Products Group 1999 All rights reserved 035 14289 000 A 1101 Code EBY L F Supersedes 035 14289 A 000 300 5005 York Drive Norman OK 73069 Unitary Products Group ...

Отзывы: