5

ADJUSTABLE FIRESTOP THIMBLE (FST-A): 

The Adjustable Firestop Thimble Assembly  (FST-A) is used 
to provide the necessary air space and clearance between the 
chimney pipe and the insulation in the attic space of a 
manufactured home. 
To install the thimble assembly, determine the distance 
between the ceiling joist and the roof framing.  Attach the 
adjustable thimble to the firestop spacer so that the assembly 
will cover the distance.  The adjustable thimble should be even 
with or above the roofline (see thimble extensions on page 11 
if a longer thimble is needed).  Sheet metal screws or staples 
may be used to attach the thimble to the firestop spacer.   
An opening large enough to allow the insertion of the firestop 
thimble assembly will be required in the ceiling.  Attach the 
firestop/thimble assembly to the ceiling/ceiling joists using 
screws or staples as shown in figure 9a.  A minimum of 8 
screws or staples should be used. 
 

The firestop thimble assembly should also be used where there 
is a cathedral ceiling, insulation barrier and roof, all in one 
assembly in a manufactured home (see figures 9b & 10).  The 
FST-A Thimble can be used in any one of three common 
ceiling pitches; flat, 12”/96”, and 30”/144”. 
An opening big enough to allow the insertion of the firestop 
thimble assembly will be required.  This opening depends on 
the pitch of your ceiling.  If your ceiling is a flat or 12”/96” 
pitch, you must use the adapter plate provided to seal 
unwanted openings since the opening in the firestop is an 
ellipse.  For 30”/144” pitch, discard the adapter. 

If the adapter is needed, secure it onto the firestop using holes 
provided (see figure 10).  The row of holes on the sides of the 
thimble is provided to allow for pitch variances.  Position the 
firestop assembly and thimble to desired angle and secure with 
screws provided.  Insert the thimble and firestop into the 
prepared opening and secure to the ceiling by nailing through 
the firestop flanges.  The thimble should be even with or 
above the roofline. Thimble extensions are available (as an 
option) when required.  See “accessories” on page 11.   

NOTE: If there is a second story in the home, firestop 
spacer 3600FS-8DM will be required.  See “Firestop 
Spacer” on page 9. 
 
PENETRATING THE ROOF: 

To maintain a 1-inch clearance to the pipe on a roof with a 
pitch, a rectangular opening must be cut. 

STEP 1:

 Determine the center point through which the pipe 

will penetrate the roof. 

STEP 2:

 Determine the center point of the roof. Pitch is the 

distance the floor drops over a given span, usually 12 inches. 
A 6/12 pitch means that the roof drops 6 inches for each 12 
inches measured horizontally down the roof.  

STEP 3:

 Use the roof-opening chart (figure 11) below to 

determine the correct opening length and flashing required. 

STEP 4:

 Remove the shingles around the opening measured 

and cut out this section. 

STEP 5:

 Add the next sections of the pipe until the end 

penetrates the roofline.  Check to see that the proper 
clearances are maintained. Extend chimney by adding sections 
of double wall pipe until pipe is a minimum of 30 inches  
above the highest point of the roof cutout. Termination and 
chimney must extend a minimum of 36 inches above the 
highest point where it passes through roof. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

IMPORTANT:

 If an exposed portion of chimney is greater 

than four feet above the roofline, use support wires to keep the 
chimney secured.  The support wires may be attached to the 
outer pipe of the chimney with screws provided the screws do 
not penetrate the inner flue pipe. 

 

 

 

 

Figure 11 

PITCH

SLOPE

OPENING "A" MAX

USE FLASHING

(degrees)

(inches)

MODEL NO.

FLAT

0

15

6F-8

0 - 6/12

26.6

16 - 1/8

6F-8

6/12 - 12/12

45.0

20 - 3/8

12F-8

Figure 10 

Figure 9a 

 

    Figure 9b 

Содержание 36ECMII

Страница 1: ...RS FULLY OPENED OR FULLY CLOSED WHEN OPERATING THIS FIREPLACE This fireplace is approved for use as a wood burning fireplace or for use with a vented gas log approved to ANS Z21 60 Z21 84 or RGA 2 72...

Страница 2: ...6 OUTSIDE AIR KIT INSTALLATION PG 4 7 FAN KIT ASSEMBLY PG 4 8 CHIMNEY PIPE INSTALLATION PG 4 5 6 9 TERMINATIONS PG 6 10 FINISHING YOUR FIREPLACE PG 7 11 MANTELS PG 7 12 GLASS DOORS PG 7 13 GAS LINE I...

Страница 3: ...s will make installation easier 4 An outside air kit is included with this fireplace For more details refer to section on outside air kit installation on page 4 WARNING DO NOT INSTALL IN A BEDROOM MIN...

Страница 4: ...f 8 beyond each side of the fireplace opening is required to protect combustible floor construction in front of the fireplace Use DESA hearth extension see accessories on page 11 HE 36 or an equal mat...

Страница 5: ...e listed under accessories on page 11 Most chimney systems for manufactured houses require a standard straight installation as described in this section If an uncommon offset installation is required...

Страница 6: ...the firestop assembly and thimble to desired angle and secure with screws provided Insert the thimble and firestop into the prepared opening and secure to the ceiling by nailing through the firestop...

Страница 7: ...top terminations In any case refer to the installation instructions supplied with the termination The terminations approved for this fireplace are the RT 8DM and RTL 8DM Figure 14 shows an RTL 8DM rou...

Страница 8: ...s must be in the FULLY OPEN or FULLY CLOSED position only or a fire hazard may be created see figure 18 A fireplace equipped with glass doors operates much differently than a fireplace with an open fr...

Страница 9: ...you wish to install an unvented vent free gas log set ONLY UNVENTED GAS LOG SETS WHICH HAVE BEEN FOUND TO COMPLY WITH THE STANDARD FOR UNVENTED ROOM HEATERS ANSI Z21 11 2 ARE TO BE INSTALLED IN THIS F...

Страница 10: ...fters or joists see figure 22 details a b 3 Maximum length of pipe between supports return elbow or 12S 8DM is 6 of angled run Maximum of two 2 6 angled run sections per chimney system see figure 24 F...

Страница 11: ...UR AUTHORIZED DEALER TECHNICAL SERVICE You may have further questions about installation operations or troubleshooting If so contact The Technical Service Department at 1 888 427 8322 When calling hav...

Страница 12: ...ouble Wall Pipe 1 3 0 18 8DM 18 Double Wall Pipe 0 0 2 FST A Adjustable Firestop Thimble 1 1 1 6F 8 Roof Flashing 1 1 1 VSC1 8DM Storm Collar 1 1 1 RTL 8DM Round Cap Termination 1 1 1 VENT KITS USE FO...

Страница 13: ...P N 035 16689 000...

Отзывы: