3.
Insert the 24VDC + and – wires (16 - 22 AWG, solid or stranded wire) from
the power supply into the 24VDC + and – terminals on the I/O module.
4.
Tighten the screw terminals with the screwdriver to secure the wire leads in
the terminal block; the maximum torque is 0.1921 Nm (1.7 in-lb).
Connect the Frame Ground Wire
Connect a frame ground wire to the I/O module’s Frame Ground terminal. Connect
the other end of the frame ground wire to frame ground.
CAUTION
:
The shield ground connections of the RS-232 port, LAN port, PoE
port, I/O port and Frame Ground terminal are internally connected. The system
grounding is designed to be at a zero ground potential; this zero ground potential
extends through the cable and to peripheral equipment (e.g. a vision system,
PLC, etc.). To ensure safe operating conditions, it is strongly recommended that
all ground connections are checked to ensure that a zero ground potential is met.
8
Содержание 821-0016-1R
Страница 1: ...In Sight CIO MICRO and CIO MICRO CC I O Modules Manual 2020October20 Revision 6 1 0 3...
Страница 2: ......
Страница 8: ...6...
Страница 20: ...l 5...
Страница 21: ...6...
Страница 32: ...5...
Страница 36: ...I O PoE In Sight Micro l l I O PoE I O 1 M12 PoE 2 RJ 45 I O PoE 3 I O 24VDC 4 In Sight I O In Sight F1 9...
Страница 38: ...0 C 45 C 32 F 113 F 10 C 65 C 14 F 149 F 11...
Страница 43: ...l Class A Class A l 5...
Страница 44: ...6...
Страница 46: ...4 0 1921Nm 1 7 I O RS 232 LAN PoE I O 0 0 PLC 0 8...
Страница 49: ...l l I O PoE I O 1 M12 PoE 2 RJ 45 I O PoE 3 I O 24VDC 4 In Sight I O F1 In Sight 11...
Страница 57: ...6...
Страница 65: ...Temp rature Fonctionnement 0 45 32 113 F Stockage 10 65 14 F 149 F 14...
Страница 71: ...6...
Страница 85: ...6...
Страница 94: ...P N 597 0129 01 Rev B Copyright 2010 2020 Cognex Corporation All Rights Reserved...