BC-7000 OPERATION
NOTE:
Before capacity testing a battery,
review all testing procedures as required by the battery
manufacturer
. Failure to do so can result in inaccurate test date.
NOTE:
Before capacity testing a battery,
RECHARGE THE BATTERY FOLLOWING THE
MANUFACTURERS RECHARGING GUIDELINES
.
NOTE:
Before putting the BC-7000 into service the REAL TIME clock must be set.
See instruction in the
BC
Report Utility
section. Failure to do so will result in incorrect printed time on test reports.
1. Make sure the power switch is in the
OFF
position. Connect the AC power cord female end into the power
receptacle located in the left rear side of the BC-7000. Connect the male end of the power cord into the AC
power outlet. Now connect the
gray
BC-7000 battery connector to the battery to be tested.
DANGER:
Never attempt to connect the BC-7000 capacity tester to a battery using anything but the proper
connector.
Doing so can damage the tester, battery, or cause injury to the operator
. Capacity testing data will be
invalid if incorrect connections are made.
2. Place the
OFF/ON
power switch to the
ON
position. The BC-7000 LCD display will flash tester model and
software version.
NOTE:
If
Replace Clock Coin Battery
is displayed on screen, remove case top and install new coin battery.
Replacement battery number is 3V #
CR2032
. Use
BC Report Utility
software to update date and time after battery