6.-Replacing a loop element
1
The first step is to know exactly which element is to be replaced.
Number of the LOOP in which it is installed
Number of the point within the loop
PROGRAMMING number of the loop element
2
Make note of the loop configuration.
Set_Up_Loop_Points
option 1
L O O P
:
0 1
A 5 0 S H / I
: 0 0 0 / 0 0 0
S I R A Y : 0 0 1
P O I N T S :
0 0 7
A 5 0 H / I
: 0 0 0 / 0 0 1
M D A x Y : 0 0 0
A 3 0 X H T C O : 0 0 0 / 0 0 0
M S T A Y : 0 0 1
A 3 0 X T A :
0 0 1
A 5 0 S / I
: 0 0 0 / 0 0 0
K M A Y : 0 0 0
3
Delete the point removed from the loop.
Set_Up_Loop_Points
option 5
4
Insert the new element (having previously made note of the point number).
5
Search loop element.
Set_Up_Loop_Points
option 2
.
When this has been completed, the configuration will be shown on the display.
Check that the configuration is the same as in step 2 above, but with the new element added.
6
Assign number to element.
Set_Up_Loop_Points
option 3
7
Whenever a modification is made, the changes should always be checked.
main menu
option 1
.
DISCONNECT the 110~230V POWER supply and the BATTERIES
before accessing the interior of the control unit.