1.0  DESCRIPTION 

Coates Spa Heaters are intended for use on spas or 
hot tubs having a forced water circulation system. 

The water flow through the heater should be at least 
15 GPM but should not exceed 70 GPM.  Higher 
flow may damage the heater.  An external bypass 
should be installed to limit the flow to within this 
range. 

2.0  INSTALLATION 

 

 

 

 

 

 

 

CHECK ELECTRICAL CONNECTIONS TO ALL 
COMPONENTS within the heater for tightness. 

 

These can become loose during shipment and 
handling. 

 

2.1  PHYSICAL PLACEMENT 

CAUTION 

 

THE ELECTRICAL INSTALLATION MUST BE IN 
ACCORDANCE WITH ARTICLE 680 OF THE 
NATIONAL ELECTRICAL CODE (NEC). 

 

The Coates Spa Heater is suitable for indoor 
installation.  See Figure 1 for piping connections 
and Figure 2 for electrical connections.  

Leave 

minimum clearance of 4 inches on the top for 
element removal and service access.

  

 

2.2  ELECTRICAL INSTALLATION 

 

The electrical supply power must be single phase, 
2 wire, 240 VAC.  The supply must be protected 
by a ground fault circuit interrupter (GFCI) in 
accordance with NEC Article 680.  An electrical 
disconnect with over-current protection must be 
provided.  An insulated ground conductor must be 
provided.  See Figure 2 for electrical connections.  
A lug has been provided for attachment of the 
BONDING wire per the NEC Article 680-22, (a)(4).  
This lug is located next to the conduit entrance.

  

WARNING 

 

Only qualified personnel, as defined by National 
Electric Code Article 100, should install and 
maintain this equipment.  Unauthorized alteration 
or improper maintenance of this unit may release 
the manufacturer from any warranty claims.  The 
installation must be in accordance with the 
instructions in this manual and applicable local 
plumbing and electrical codes. 

** NOTICE **

NO PRESSURE RELIEF 

VALVE IS SHIPPED WITH 

THIS HEATER AND NONE 

IS REQUIRED PER UL 

STD 1261.  DO NOT 

INSTALL SHUT OFF 

VALVE BETWEEN THE 

HEATER AND POOL OR 

SPA.  A CHECK VALVE IS 

ACCEPTABLE AND IN 

ACCORDANCE TO UL STD 

1261 REVISED JULY 1983.

COATES POOL 

HEATER

FILTER

POOL 

or 

SPA

CHECK 

VALVE

DRAIN 
VALVE

BALL OR GATE 

VALVE

PUMP

BALL OR GATE 

VALVE

CAUTION

DO NOT INSTALL ANY SHUT-OFF 
VALVE ON DISCHARGE SIDE OF 
HEATER.  A SWING CHECK 
VALVE IS PERMITTED.

Exception:  If a 30 psi (2.1 Kg/cm

2

pressure relief valve is installed 
between the heater and valve , the 
valve may be of the shut-off (ball or 
gate) type.

FIGURE 1 – PIPING DIAGRAM 