Page 11
Technical information CN80 / 120 boiler installed with 80/120 kW CN Stoker
•
Smoke gas temperature 80 / 120 boiler at nominal yield with wood pellets: 142 /
134
°C
•
Smoke gas temperature 80 / 120 boiler at 20 % yield with wood pellets: 78 / 83
°C
•
Smoke gas mass flow 80 / 120 boiler at nominal yield: 140 / 229 kg/h
•
Smoke gas mass flow 80 / 120 boiler at partial load 20 % yield: 54.8 / 88 kg/h
•
Nominal yield 80 / 120 boiler in nearest whole kW with wood pellets: 82 / 117
kW
•
Yield range 80 / 120 boiler 20 % -100 %:16.7-82 / 32-117kW
•
Required flue 80 / 120 boiler 14 Pa
•
Chimney must have an internal diameter of minimum 250mm and be of an
approved type.
•
The boiler thermostat setting range is 55-85 °C
•
Water content in 80 / 120 boiler: 490 / 560 L.
•
Boiler classification: 3
•
Set point for boiler thermostat: 65 °C
Warranty Claims
CN MASKINFABRIK A/S provides a 24 month warranty for the stoker unit following the
date of this user manual for the first user.
The warranty includes materials and manufacturing faults, but not wear on parts, damages
caused by failure to maintain the unit, incorrect use or overloading.
Claims will be compensated based on the price of the spare parts or repair, if this is
cheaper. Labour wages according to an hourly labour rate for normal working hours as
specified by CN MASKINFABRIK A/S.
The warranty does not cover transport, freight, consequential damages and operational
losses.
This warranty is not valid until CN MASKINFABRIK A/S has received the check list
on p. 14.