CM-P3/ CM-EP3

                                        

 

Conventional Fire Alarm Control Panel

             

        

    

Yun Yang Fire Safety Equipment

 

 

 

Manual Book

   

                           

     

 

 

 

 

 

F. Specification 

Item 

Specification 

Model   

CM-P3 / CM-EP3 

Category 

Conventional Fire Alarm Control Panel 

Type 

Wall-mount 

Power Source 

240V AC 50 / 60 Hz 

±

10

 

Standby Battery 

24V DC 

Charging Voltage  Below 26V DC 450mA, trickle charging 
Circuit Voltage 

24V DC operation voltage, under 10~11V DC 32mA 

Rated Impedance  Below 50Ω 

Detector 
Connection 

No limitation for Conventional Rate of Rise or Fixed 
Temperature Heat Detectors; Up to 30 Photoelectric Smoke 
Detectors can be connected per zone                   
(monitor current for detectors : 24V DC 40μA) 

E.O.L Resistor 

10KΩ 

No. of Indicators

 

The same as the number of zones (LED indicating lamp)

 

No. of Bells

 

The same as the number of zones

 

Color 

Red 

Buttons 

Push-button 

Cabinet Material 

Powder coating steel (up to 24L only)

 

/                     

Flame retardant ABS enclosure (up to 32L only)

 

Main Audio

 

Mono tone sounder (above 85dB for 1m distance)

 

Alarm Relay 
Contact 

No-Voltage NO contact, capacity 250V AC / 7A 

 

Содержание CM-EP3

Страница 1: ...CM P3 CM EP3 Conventional Fire Alarm Control Panel Manual Book 2016 03 02 REV 1 71114 023 E...

Страница 2: ...nual Book CONTENTS Metal Cabinet Dimensions 2 Plastic Cabinet Dimensions 3 Description 4 Electric Characteristics 4 Panel Functions 4 Specification 7 Basic Troubleshooting 8 Fuse Specification 9 Wirin...

Страница 3: ...nel Yun Yang Fire Safety Equipment 2 Manual Book A Metal Cabinet Dimensions Size Number of zone H mm W mm D mm 1L 2L 4L 5L 8L 330 280 120 12L 16L 400 300 120 20L 24L 495 300 120 Box size according to...

Страница 4: ...Yun Yang Fire Safety Equipment 3 Manual Book B Plastic Cabinet Dimensions Size Number of zone H mm W mm D mm 1L 2L 4L 5L 8L 260 330 96 12L 16L 20L 400 300 126 24L 28L 32L 370 480 90 Box size according...

Страница 5: ...32V Charging Method Tickle Charging at Rated Voltage E Panel Functions As the control unit turns on the POWER light is on Fire Alarm When the specific zone received an in coming signal and confirm tha...

Страница 6: ...ned the control unit will lock the state of ZONE FIRE light FIRE indicator BELL sound bell ring on the spot reporting contact point C NO Press SIGNAL HOLD DISABLE button to release the lock As the det...

Страница 7: ...e ZONE SHORT CIRCUIT light on indicating detector short circuit happened in specific zone AC POWER FAULT light on indicating battery charging is abnormal BATTERY FAULT light flashes indicating battery...

Страница 8: ...ce Below 50 Detector Connection No limitation for Conventional Rate of Rise or Fixed Temperature Heat Detectors Up to 30 Photoelectric Smoke Detectors can be connected per zone monitor current for det...

Страница 9: ...ry power in working normally 2 Check whether Fuse 1 Fuse 2 or Fuse 3 is burned If so please replace with a new fuse 2 The indicator of Battery Fault flashes Check whether the barrery and Fuse 2 are wo...

Страница 10: ...r 2 Fuse F3 1A Fuse BATTERY 2A Fuse AC 1A ZONE 9 TO ZONE 16 Charging Voltage F1 3A Sounder 1 Fuse F2 1 5A Sounder 2 Fuse F3 1 5A Fuse BATTERY 3A Fuse AC 1A ZONE 17 TO ZONE 24 Charging Voltage F1 4A So...

Страница 11: ...CM P3 CM EP3 Conventional Fire Alarm Control Panel Yun Yang Fire Safety Equipment 10 Manual Book I Wiring Diagram of the Central Control unit 1 1 8L...

Страница 12: ...CM P3 CM EP3 Conventional Fire Alarm Control Panel Yun Yang Fire Safety Equipment 11 Manual Book 2 9 16L...

Страница 13: ...CM P3 CM EP3 Conventional Fire Alarm Control Panel Yun Yang Fire Safety Equipment 12 Manual Book 3 17 24L...

Страница 14: ...CM P3 CM EP3 Conventional Fire Alarm Control Panel Yun Yang Fire Safety Equipment 13 Manual Book 4 25 32L...

Отзывы: