7 - CONTROL
CIRCUIT 1 STATA - TAB 2
code
description
description
DO-985
Cmd YVDW_DO2
Decreasing power valve (CR2_Bitzer) (15_RefComp) (screw compressor only): 0=Off 1=On
S1100
CMP1 starts
Compressor 1 starts
S1101
CMP2 starts
Compressor 2 starts
S1102
CMP3 starts
Compressor 3 starts
S1103
StartsScrew
Screw compressor starts
S1104
Source starts
Source starts
S1105
Hours Comp.1
Hours Compressor 1
S1106
Hours Comp.2
Hours Compressor 2
S1107
Hours Comp.3
Hours Compressor 3
S1108
HoursScrew
Hours screw compressor
S1109
HoursSource
Hours Source
S1110
Total steps
Total steps engaged on the circuit
S1111
Comp.1 status
Compressor 1: 0=free 1=on 2=timing 3=Disabled
S1112
Comp.2 status
Compressor 2: 0=free 1=on 2=timing 3=Disabled
S1113
Comp.3 status
Compressor 3: 0=free 1=on 2=timing 3=Disabled
S1114
Current cap.
Current capacity engaged on the circuit
S1115
Requested cap.
Requested capacity on the circuit
S1116
Pressure ratio
Pressure ratio (1+Hp/1+LP)
S1117
FANPreAlarm
Max. fan pre-alarm 0=Off 1=On
S1118
Defrost delay
Actual value defrost counting (0= defrost starting)
S1119
Defrost status
Defrost status : 0=Defrost Off, 1=Defrost ON
S1120
HWErr
Hardware fault POL94U module : handling possible
S1121
BlckingHWErr
Hardware fault POL94U module handling impossible
S1122
FailSafeSta
Safe status : 0=Off 1=On
S1123
UPSNotAval
UPS faulty : 0=Off 1=On
S1124
CircWarning
Circuit warning
S1125
CircBlock
Circuit alarm
S1126
ThTDischarge
Estimated discharge temperature