ACCESSIBLE PARAMETERS FROM REMOTE OR SERVICE KEYBOARD
num.
Par.
description Value
UM
29
Summer secondary Set Point
10 °C
30
Winter secondary Set Point
35
°C
32
Summer Set Point
5.7
°C
33
Winter Set Point
41.2
°C
42
Summer Set Point Maintenance
20
°C
43
Winter Set Point Maintenance
30
°C
44
Enables Summer Maintenance
0
num
45
Enables Winter Maintenance
0
num
77
Antifreeze heater set point
4
°C
80 Antifreeze
alarm
4 °C
84
Limit of deactivation before reaching the antifreeze steps
4.5
°C
163
Configures remote inputs: 1 = H/C by keypad or supervisor
192 Keypad
address
PARAMETER MODIFICATION
1
AL
ARM
ST
AT
US
SE
T
Push SET button
2
AL
AR
M
ST
AT
US
SE
T
Select the
parameter
3
AL
AR
M
ST
AT
US
SE
T
Modify the value
4
AL
ARM
ST
ATU
S
SET
Select another
parameter
5
AL
AR
M
ST
AT
US
SE
T
SET to esc
VISIBLE STATUS FROM REMOTE KEYBOARD OR SERVICE KEYBOARD
Visible status from remote keyboard or service keyboard
INDEX DESCRIPTION
VALUE
1
Current Set Point
°C
2
Temperature drop in degrees centigrade given by the compressor including
compensations, if any
°C
3
Resource activation timer
When this value reaches the value fixed at the 4 status, the thermal regulator will
compare the input temperature with the set point and will activate the resources, if
necessary
Seconds
4
Dynamic TimeScan relating to source activation
Seconds
5
Value in degrees of the external air compensation
°C
6
Value in degrees of the water reset signal compensation
°C
7
Value in degrees of the charge compensation
°C
9
Inlet temperature
°C
10
Outlet temperature 1
°C
11
Outlet temperature 2
°C
12
Coil temperature 1
°C
13
Condensing pressure 1
Bar
14
Fan/Coil percentage 1
0-100%
15
Coil temperature 2
°C
16
Condensing pressure 2
Bar