SIZE
SOUND POWER LEVEL (dB) - Octave band (HZ)
Sound power level
Sound pressure level
63
125
250
500
1000
2000
4000
8000
dB(A)
dB(A)
120.1
54
53
70
81
98
87
72
58
79
99
160.1
55
54
70
82
99
88
73
58
80
99
200.1
64
57
83
89
98
89
79
68
79
99
240.1
67
72
78
85
99
86
82
65
79
99
290.1
50
58
78
92
97
93
82
68
79
100
250.2
69
72
74
86
99
89
76
62
79
100
280.2
69
72
75
86
99
90
77
62
80
100
320.2
70
73
75
87
100
90
77
62
80
101
360.2
80
88
81
90
100
90
85
68
80
101
400.2
81
89
82
91
102
91
86
69
82
103
440.2
71
77
82
97
102
96
86
72
82
103
480.2
84
93
85
93
102
90
89
71
81
103
540.2
82
90
85
98
101
96
89
73
81
103
580.2
68
79
85
100
101
98
89
75
82
104
sound levels - Standard acoustic configuration (ST)
sound levels - Compressor soundproofing (SC)
SIZE
SOUND POWER LEVEL (dB) - Octave band (HZ)
Sound power level
Sound pressure level
63
125
250
500
1000
2000
4000
8000
dB(A)
dB(A)
120.1
55
53
69
77
96
82
71
55
77
96
160.1
56
54
69
78
97
82
72
56
78
97
200.1
66
56
82
85
96
84
78
65
77
97
240.1
68
71
77
81
96
82
80
62
77
97
290.1
52
57
77
87
95
88
80
65
76
97
250.2
70
71
73
82
97
84
76
59
76
97
280.2
71
72
74
83
97
84
76
59
77
98
320.2
71
72
74
83
98
85
76
60
77
98
360.2
81
86
79
85
97
85
82
63
77
98
400.2
83
88
81
87
100
87
84
66
79
100
440.2
72
76
81
92
99
90
84
68
79
100
480.2
86
92
84
89
100
87
87
68
79
100
540.2
83
89
84
93
99
90
87
70
79
101
580.2
70
78
84
95
99
92
87
71
78
101
Sound levels refer to full load units, in test nominal conditions. The sound pressure level refers to 1 m. from the standard unit outer surface operating in open field. Measures
according to UNI EN ISO 9614-2 regulations, with respect to the EUROVENT 8/1 certification, which provides for a tolerance of 3 dB(A).
Data referred to the following conditions:
- internal exchanger water temperature = 12/7 °C
- ambient temperature = 35 °C
Sound levels refer to full load units, in test nominal conditions. The sound pressure level refers to 1 m. from the standard unit outer surface operating in open field. Measures
according to UNI EN ISO 9614-2 regulations, with respect to the EUROVENT 8/1 certification, which provides for a tolerance of 3 dB(A).
Data referred to the following conditions:
- internal exchanger water temperature = 12/7 °C
- ambient temperature = 35 °C
General technical data
60
Содержание WDAT-iZ4
Страница 1: ...R1234ze MANUAL FOR INSTALLATION USE AND MAINTENANCE WDAT iZ4 120 1 580 2 ...
Страница 18: ...18 5 ELECTRICAL CONNECTIONS ...
Страница 32: ...32 7 CONTROL ...
Страница 33: ...33 7 CONTROL ...
Страница 34: ...34 7 CONTROL ...
Страница 35: ...35 7 CONTROL ...
Страница 36: ...36 7 CONTROL ...
Страница 37: ...37 7 CONTROL ...
Страница 38: ...38 7 CONTROL ...
Страница 39: ...39 7 CONTROL ...
Страница 51: ...51 Compressor replacement 8 MAINTENANCE ...
Страница 52: ...52 9 ANTIVIBRATION MOUNTS Anti vibration mount support Anti seismic spring antivibration mounts ...
Страница 53: ...53 9 ANTIVIBRATION MOUNTS ...
Страница 54: ...54 9 ANTIVIBRATION MOUNTS ...
Страница 71: ......