FF144:
Minimum compression ratio
Logico
M
fF145:
Maximum engine torque
Logico
A/M
iI002:
Low water pressure
DI
687 central
T5 DU1
A/M
iI006:
Flow switch utility side
DI
687 central
T3 X8
A/M
II007:
Freeze alarm utility side
M
ii008:
Utility side pumps On for antifreeze alarm
A
II009:
COOL:
outlet temperature higher than inlet temperature
HEAT:
inlet temperature higher than outlet temperature
A
iI120:
Flow switch source side
DI
985 circuit 1
T2 X4
A/M
II121:
Freeze alarm source side
A
II042:
FCI module, system pressure
DI
955 FCI
X3
M
II043:
FCI module, antifreeze alarm
Logico
955 FCI
X1
M
ii047:
FCI module, water flow alarm
DI
955 FCI
X4
A
ii052:
Recosery module, flow alarm
DI
965 REC
X6
A
ii053:
Recovery module, system pressure
DI
965 REC
X6
A
14.2 Status
The status code identifies the concerned circuit:
Example:
S 1 100:CMP1 compressor1 starts = circuit 1
S 2 100:CMP1 compressor1 starts = circuit 2
The number of refrigerant circuits depends on series and size of the unit.
Example:
AI-687 T.IN H2OUtil_B1 Inlet water temperature
AI = analogic input
687 = main module
B1 = PIN
14.3 General stata and central module
code
description
detailed description
AI-687
T.IN H2OUtil_B1
Inlet water temperature utility side
AI-687
T.OUT H2OUtil_B2
Outlet water temperature user side
AI-687
Ext.Air temp_B3
Outdoor air temperature
AI-687
S.DemandLimit_X1
Signal of the demand limit function controls
AI-687
S.WaterReset_X2
Signal of the water reset function controls
AI-687
RHExt_X3
Outside relative humidity
AI-687
El.CabinetTemp_X4
Electrical panel temperature
AO-687
%FREE-COOLING _X5 Percentage value of the status of the external control signal of the ventilation/FREE-COOLING valve
DI-687
Sel.SetPoint_DU2
Status of the second digital input setpoint 0=1°set 1=2°Set
DI-687
SystemPressure_DU1 Status of the system water pressure sensor 0=OK 1=Fault
DI-687
FlowUser_X8
Status of the differential pressure switch/utilisation flow 0=OK 1=Fault
DI-687
ON-OFFRem_X7
Status of the unit status digital input 0=OFF 1=On
DI-687
Heat/CoolRem_X6
Status of the unit mode digital input 0=Heat 1=Cool
DI-687
PhaseMonitor_DL1
Status of the phase monitor input 0=OK 1=Fault
DI-687
OvlP1Util_D2
Status of thermal protection contact of utilisation pump 1 0=OK 1=Fault
DI-687
OvlP2Util_D1
Status of thermal protection contact of utilisation pump 2 0=OK 1=Fault
DI-687
OvlP3Util_DL2
Status of thermal protection contact of utilisation pump 3 0=OK 1=Fault
DO-687
El.CabinetFAN_DO1
Status of the ventilation control of the electrical panel: 0=Off 1=On
DO-687
El.CabinetHEAT_DO2
Status of the heating control of the electrical panel: 0=Off 1=On
DO-687
UnitMode_Q1
Status of the digital output related to the operating mode (N.O. Open=Cool N.O. Closed=Heat): 0=Cool 1=Heat