BT15B012GB-00
ELFOFresh²
23
General technical data
Size
70
120
200
300
500
650
Cooling AE 30°C
Cooling capacity
1
kW
0,43
0.81
1.57
2.10
3.01
4.03
Compressor power input
1
kW
0,16
0,28
0.50
0.64
0.92
1.29
Total power input
1
kW
0,19
0.31
0.54
0.70
1.04
1.48
EER
1
2,27
2.58
2.90
3.00
2.91
2.72
Cooling AE 35°C
Cooling capacity
2
kW
0.45
0.85
1.63
2.17
3.13
4.23
Compressor power input
2
kW
0.17
0.30
0.52
0.67
0.98
1.33
Total power input
2
kW
0.20
0.33
0.57
0.73
1.10
1.60
EER
2
kW
2.24
2.54
2.87
2.96
2.86
2.78
Heating AE 7°C
Heating capacity
3
kW
0.52
0.98
1.81
2.33
3.58
5.00
Compressor power input
3
kW
0.14
0.23
0.40
0.54
0.75
1.12
Total power input
3
kW
0.15
0.25
0.44
0.59
0.84
1.27
COP
3
3.38
3.90
4.10
3.93
4.27
3.94
Heating AE -5°C
Heating capacity
4
kW
0.52
0.97
1.86
2.35
3.74
5.10
Compressor power input
4
kW
0.11
0.189
0.32
0.38
0.58
0.85
Total power input
4
kW
0.12
0.21
0.36
0.43
0.67
1.00
COP
4
4.17
4.74
5.17
5.45
5.57
5.12
Compressor
Type of compressors
ROT
ROT
ROT
ROT
ROT
ROT
No. of compressors
No
1
1
1
1
1
1
Type of refrigerant
R-134a
R-134a
R-410A
R-410A
R-410A
R-410A
Refrigerant charge
Kg
0,32
0,21
0,80
0,75
1,00
1,45
Fans
Type of fans
CFG
CFG
CFG
CFG
CFG
CFG
Number of fans
No
2
2
2
2
2
2
Airflow
mch
70
120
200
300
480
650
Fan power input
5
kW
0,014
0,017
0,040
0,052
0,090
0,150
Available nominal pressure
Pa
40
40
40
40
40
40
Max external static pressure
Pa
120
120
120
120
120
120
Connections
Condensate drain
mm
16
16
26
26
26
26
Power supply
Standard power supply
V
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
Noise Levels
Sound pressure level (1 m)
6
dB(A)
37
38
39
41
44
46
1 - AE 30°C: Data referred to the following conditions:
outdoor air temperature 30°C DB/22°C WB
internal air temperature 27°C DB/19°C WB
Nominal air flow
4 - AE –5°C:Data referred to the following conditions:
fresh air temperature: -5°C BS/ -5.4°C BU
internal air temperature 20°C DB/15°C WB
Nominal air flow
2 - AE 35°C: Data referred to the following conditions:
fresh air temperature: 35°C BS/ 24.0°C BU
internal air temperature 27°C DB/19°C WB
Nominal air flow
5 - the fan absorptions refer to the air flows of the heating operation (conditions as
indicated in note (3)) and 40Pa of available pressure
3 - AE 7 °C:Data referred to the following conditions:
outdoor air temperature 7°C DB/6°C WB
internal air temperature 20°C DB/15°C WB
Nominal air flow
6 - Sound levels refer to units with full load under nominal test conditions.
The sound pressure level refers to a distance of 1 meter from the outer surface of the
unit operating in open field.
Содержание ELFOFresh2 CPAN-U 70-120 Series