5.2 Some connectors introduce:

 

A For remote control (ON-OFF) terminal  port CN23 and short connector of JR6
1. Remove the short connector of JR6 when you use ON-OFF function;
2. When remote switch off (OPEN) ;the unit would be off;
3. When remote switch on (CLOSE) ;the unit would be on;
4. When close/open  the remote switch, the unit would be responded the demand within 2 seconds;
5. When the remote switch on. you can use remote controller/ wire controller to select the mode 
what you want ;when the remote switch off , the unit would not respond the demand from remote 
controller/wire controller.
when the remote switch off , but the remote controller / wire controller are on, CP code would be 
shown on the display board.
6.The voltage of the port is 12V DC , design Max.current is 5mA.

Содержание Box-SL IB2-XY 35M

Страница 1: ...TECHNICAL MANUAL 18 01 2019 TM19A066GB 00 LIGHT COMMERCIAL R32 CASSETTE 650x650 Box SL 2 Outdoor unit SL 2 Only size 53M ...

Страница 2: ... Curves 10 Electrical Characteristics 2 Product Features 28 1 Operation Modes and Functions 2 Remote Controller Functions 3 Installation 39 1 Installation Overview 2 Location Selection 3 Indoor Unit Installation 4 Outdoor Unit Installation 5 Drainage Pipe Installation 6 Refrigerant Pipe Installation 7 Vacuum Drying and Leakage checking 8 Additional Refrigerant Charge 9 Engineering of Insulation 10...

Страница 3: ...Dimensional Drawings 7 4 Centre of Gravity 9 5 Electrical Wiring Diagrams 10 6 Refrigerant Cycle Diagrams 20 7 Capacity Tables 21 8 Capacity Correction Factor for Height Difference 24 9 Noise Criterion Curves 25 10 Electrical Characteristics 27 Specifications ...

Страница 4: ...ference Refer to the following table to determine the specific indoor and outdoor unit model number of your purchased equipment Outdoor Unit Model indoor Unit Model Capacity Btu h Power Supply MC2 Y 53M IB2 XY 53M 18k 1ɸ 220 240V 50Hz ...

Страница 5: ...ndoor sound pressure level dB A 42 5 39 35 5 Indoor sound power level dB A 56 Indoor unit Dimension W x Dx H body mm 570x570x260 Packing W x Dx H body mm 662x662x317 Dimension W x Dx H panel mm 647x647x50 Packing W x Dx H panel mm 715x715x123 Net Gross weight body kg 16 2 21 4 Net Gross weight panel kg 2 5 4 5 Drainage water pipe dia mm ODɸ25mm Refrigerant piping Liquid side Gas side mm ɸ6 35 ɸ12 ...

Страница 6: ...ge kg 1 15 Design pressure MPa 4 3 1 7 Refrigerant piping Liquid side Gas side mm inch ɸ6 35 ɸ12 7 1 4 1 2 Max pipe length m 30 Max difference in level m 20 Ambient temperature Cooling 15 50 Heating 15 24 Qty per 20 40 40 HQ Outdoor unit 108 219 292 Notes 1 Capacities are based on the following conditions Cooling T1 Indoor Temperature 27 C 80 6 F DB 19 C 66 2 F WB Heating Indoor Temperature 20 C 6...

Страница 7: ...Specifications Page 7 3 Dimensional Drawings Indoor Unit Cassette 650x650 BOX SL 2 ...

Страница 8: ...Specifications Page 8 Model Unit W D H W1 A B C MC2 Y 53M mm 800 333 554 870 514 340 365 inch 31 49 13 11 21 81 34 25 20 23 13 39 14 37 ...

Страница 9: ...Specifications Page 9 4 Centre of gravity MC2 Y 53M ...

Страница 10: ...door unit Abbreviation Paraphrase Y G Yellow Green Conductor CAP1 Indoor Fan Capacitor FAN1 Indoor Fan L LIVE N NEUTRAL TO CCM Comm Bus Central Controller T1 Indoor Room Temperature T2 Coil Temperature of Indoor Heat Exchanger P3 Super High Speed P2 High Speed ...

Страница 11: ... Bus CN7 T2B OUTER PIPE TEMP POWER P1 CN3 JR6 JR6 FAN1 CAP1 Y G P3 P2 6 CN4 2 H CH P4 Y G 4 BROWN BLACK CN110 YELLOW Y G TO OUTDOOR UNIT P5 MAGNETIC RING MAGNETIC RING NOTE The wiring diagram is for explanation purpose only The actual shape of the components may be different 16022500004023 WIRING DIAGRAM INDOOR UNIT SWITCH FOR COOLING HEATING SW7 ON STATE MODE COOLING HEATING COOLING ONLY ON ON Fa...

Страница 12: ...be on 4 When close open the remote switch the unit would be responded the demand within 2 seconds 5 When the remote switch on you can use remote controller wire controller to select the mode what you want when the remote switch off the unit would not respond the demand from remote controller wire controller when the remote switch off but the remote controller wire controller are on CP code would b...

Страница 13: ...RM but no voltage of the terminal port the power from the ALARM system not from the unit 2 Although design voltage can support higher voltage but we strongly ask you connect the power less than 24V current less than 0 5A 3 When the unit occurs the problem the relay would be closed then ALARM works ...

Страница 14: ...e output voltage is the power supply 3 The fresh motor can not excess 200W or 1A follow the smaller one 4 The new fresh motor will be worked when the indoor fan motor work when the indoor fan mo tor stops the new fresh motor would be stopped 5 When the unit enter force cooling mode or capacity testing mode the fresh motor isn t work ...

Страница 15: ...anti cold wind action in heating mode Range 24o C 15o C 8o C According to EEROM setting reserved for special customizing B Micro switch SW2 is for selection of indoor FAN ACTION if room temperature reaches the setponit and the compressor stops Range OFF anti cold wind is available in heating mode Keep running No anti cold wind function ...

Страница 16: ...s for selection of temperature compensation in heating mode This helps to reduce the real temperature difference between ceiling and floor so that the unit could run properly If the height of installation is lower smaller value could be chosen Range 6o C 4o C 2o C E function reserved for special customizing SWITCH FOR COOLING HEATING SW7 ON STATE MODE COOLING HEATING COOLING ONLY ON ON Factory Set...

Страница 17: ...B D E F 0 8 4 1 2 3 5 6 7 C 9 A B D E F 0 8 4 1 2 3 5 6 7 C 9 A B D E F 0 8 4 1 2 3 5 6 7 C 9 A B D E F 20 26 36 53 32 35 54 71 72 90 91 105 141 160 H Dial switch ENC1 The indoor PCB is universal designed for whole series units from 7K to 68K This ENC1 setting will tell the main program what size the unit is NOTE Usually there is glue on it because the switch position cannot be changed at random u...

Страница 18: ...T1 CT2 AC Current Detector COMP Compressor L PRO Low Pressure Switch H PRO High Pressure Switch L PFC Inductor SV 4 Way Valve TRANS Power Transformer TP Exhaust Temperature Sensor T4 Outdoor Ambient Temperature Sensor T3 Condenser Temperature Sensor TH Heatsink Temperature Sensor XT1 2 Way Terminal 4 Way Terminal XT2 3 Way Terminal XT4 Terminal EEV Electronic Expansion Valve D Diode Module ...

Страница 19: ...IT S 2 N L N RED BLUE OR BLACK 1 L Y G AMBIENT TEMP SENSOR DISCHARGE TEMP SENSOR CN 21 CONDENSER TEMP SENSOR Y G COMPRESSOR U V W BLUE RED BLACK BLUE RED WHITE CN 25 MAIN BOARD CN 1A CN 3 CN 1 CN 2 CN 16 CN 50 CN 30 CN 29 CN 28 BLUE RED BLACK REACTOR 1005AL OPTIONAL BLUE OR WHITE BLUE OR WHITE CN 9 CN 32 POWER SUPPLY Y G Notes This symbol indicates the element is optional the actual shape shall be...

Страница 20: ... 6 Refrigerant Cycle Diagrams Model No Pipe Size Diameter ø mm inch Piping length m ft Elevation m ft Additional Refrigerant Gas Liquid Rated Max Rated Max MC2 Y 53M 12 7 1 2 6 35 1 4 5 16 4 30 98 4 0 20 65 6 12g m 0 13oz ft ...

Страница 21: ... 5 79 5 79 5 79 5 79 6 19 6 19 6 19 6 19 S T 0 69 0 76 0 83 0 89 0 57 0 63 0 70 0 76 0 51 0 58 0 64 0 70 0 38 0 44 0 50 0 56 PI 1 14 1 14 1 14 1 14 1 14 1 14 1 14 1 14 1 14 1 14 1 14 1 14 1 13 1 13 1 13 1 13 20 TC 5 24 5 24 5 24 5 30 5 56 5 56 5 56 5 56 5 73 5 73 5 73 5 73 6 13 6 13 6 13 6 13 S T 0 69 0 76 0 83 0 89 0 57 0 63 0 70 0 76 0 51 0 58 0 64 0 70 0 38 0 44 0 50 0 56 PI 1 18 1 18 1 18 1 18...

Страница 22: ... 12 2 12 2 14 2 14 2 14 2 14 720 15 TC 5 74 5 74 5 80 5 86 6 05 6 05 6 05 6 05 6 20 6 20 6 20 6 20 6 57 6 57 6 57 6 57 S T 0 70 0 78 1 00 1 00 0 56 0 64 0 72 0 98 0 49 0 57 0 66 0 73 0 35 0 42 0 49 0 57 PI 1 14 1 14 1 14 1 14 1 13 1 13 1 13 1 13 1 13 1 13 1 13 1 13 1 12 1 12 1 12 1 12 10 TC 5 71 5 71 5 77 5 83 6 02 6 02 6 02 6 02 6 17 6 17 6 17 6 17 6 55 6 55 6 55 6 55 S T 0 70 0 79 1 00 1 00 0 56...

Страница 23: ... 76 1 78 7 0 4 63 4 60 4 57 4 54 1 84 1 90 1 87 1 89 5 6 4 67 4 64 4 61 4 59 1 80 1 82 1 83 1 84 2 8 4 70 4 64 4 64 4 61 1 72 1 73 1 74 1 75 0 0 4 67 4 61 4 59 4 56 1 64 1 65 1 65 1 66 2 8 4 82 4 76 4 73 4 70 1 57 1 58 1 58 1 59 5 6 5 11 5 05 5 02 4 99 1 50 1 51 1 51 1 51 7 0 5 43 5 36 5 28 5 25 1 48 1 45 1 49 1 49 11 1 5 60 5 51 5 48 5 45 1 37 1 37 1 37 1 37 13 9 5 71 5 65 5 60 5 57 1 30 1 30 1 2...

Страница 24: ...937 0 921 5 0 995 0 979 0 946 0 930 0 1 000 0 984 0 951 0 935 Outdoor Upper than Indoor 5 1 000 0 984 0 951 0 935 10 0 984 0 951 0 935 20 0 951 0 935 Heating 5 10 20 30 Height difference H m Indoor Upper than Outdoor 20 0 982 0 976 10 0 994 0 982 0 976 5 1 000 0 994 0 982 0 976 0 1 000 0 994 0 982 0 976 Outdoor Upper than Indoor 5 0 992 0 986 0 974 0 968 10 0 978 0 966 0 960 20 0 959 0 953 ...

Страница 25: ... acoustic pressure OdB 20µPa Sound level will vary depending on a range of factors such as theconstruction acousticabsorptioncoefficient ofparticular room in which the equipment is installed The operating conditions are assumed to be standard IB2 XY 53M 0 10 20 30 40 50 60 70 80 63 125 250 500 1000 2000 4000 8000 Octave Band Sound Pressure Level dB 0dB 0 0002μbar Band Center Frequency Hz H M L NC ...

Страница 26: ...ic pressure OdB 20µPa Sound level will vary depending on arrange off actors such as the construction acoustic absorption coefficient of particular room in which the equipment is installed The operating conditions are assumed to be standard MC2 Y 53M 0 10 20 30 40 50 60 70 80 63 125 250 500 1000 2000 4000 8000 Octave Band Sound Pressure Level dB 0dB 0 0002μbar Band Center Frequency Hz Cooling Heati...

Страница 27: ...se Frequency and Voltage 220 240V 50Hz Circuit Breaker Fuse A 25 20 Indoor Unit Power Wiring mm2 Outdoor Unit Power Wiring mm2 3 2 5 Indoor Outdoor Connecting Wiring mm2 Ground Wiring 2 5 Strong Electric Signal 4 1 0 4x2 5 with auxiliary electric heater Weak Electric Signal ...

Страница 28: ...rying Mode 32 1 9 Forced Operation Function 32 1 10 Timer Function 32 1 11 ECO Function 32 1 12 Auto Restart 32 1 13 Drain Pump Control 33 1 14 8 C Heating Control optional 33 1 15 Self clean Control optional 33 1 16 Follow Me optional 33 1 17 Silence Control optional 33 2 Remote Controller Functions 34 2 1 LCD Wired Remote Controller 34 2 2 Centralized Controller 38 Product Features ...

Страница 29: ...ler wired controller or central controller must be used to clear the fan fault and fault count The fan runs normally for 5 minutes while clearing fault count 0 No malfunction 1 P0 Overcurrent 2 Overpressure 3 Overload 4 Over speed 5 Startup malfunction 6 Lack of phase 7 DC voltage too low 8 Communication fault 9 Parameter fault 10 L3 Current limited 11 L5 Voltage limited 12 Target speed cannot be ...

Страница 30: ...ture Turbo or sleep function on off Various frequency limit shutdown occurs 1 5 2 Indoor Fan Control 1 In cooling mode the indoor fan operates continuously The fan speed can be set to 1 100 or low medium high and auto 2 Auto fan action in cooling mode Descent curve When T1 Tsc is lower than or equal to 3 5 C fan speed reduces to 80 When T1 Tsc is lower than or equal to 1 C fan speed reduces to 60 ...

Страница 31: ...than 0 5 C fan speed reduces to 40 When T1 Tsc is higher than 1 C fan speed reduces to 20 Descent curve When T1 Tsc is lower than or equal to 0 5 C fan speed increases to 20 When T1 Tsc is lower than or equal to 0 C fan speed increases to 60 When T1 Tsc is lower than or equal to 1 5 C fan speed increases to 80 When T1 Tsc is lower than or equal to 3 C fan speed increases to 100 1 6 3 Outdoor Fan C...

Страница 32: ... fan speed sleep mode Follow me 1 10 Timer Function The timing range is 24 hours Timer On The machine turns on automatically at the preset time Timer Off The machine turns off automatically at the preset time Timer On Off The machine turns on automatically at the preset On Time and then turns off automatically at the preset Off Time Timer Off On The machine turns on automatically at the preset Off...

Страница 33: ...ing auto cooling or auto drying mode The indoor unit will run in low fan mode for a certain time then ceases operation Self Clean keeps the indoor unit dry and prevents mold growth When match with multi outdoor unit this function is disabled 1 16 Follow me Optional If you press Follow Me on the remote the indoor unit will beep This indicates the follow me function is active Once active the remote ...

Страница 34: ...ing or call up the menu 11 BACK button Back to previous operation or superior menu 12 COPY button Copy timer setting of one day to another in weekly schedule setting 13 Infrared remote receiver on some models 1 POWER button Turn on of turn off the unit 2 MODE A B button Usedtoselecttheoperationmode Auto Cooling Drying Heating Fan Hold to active the operation of auto lifting panel when off 3 Adjust...

Страница 35: ...2 Room temperature indication 13 Clock display 14 On Off timer 15 Timer display 1 Operation mode indication 2 Fan speed indication 3 Left right swing indication 4 Up down swing indication 5 Faceplate function indication 6 Main unit and secondary unit indication 7 Follow me function indication Product Features ...

Страница 36: ...inboard CN40 Wire controller Indoor unit mainboard 4 Core Shield Cable the length is decided by installation Installation Diagram Connect the female joint of wires group from the mainboard with the male joint of connective wires group Then connect the other side of connective wires group with the male joint of wires group leads from wire controller Mainboard 4 core shielding wire The connection ca...

Страница 37: ...sed mounting four outletting positions There are three need cutting Cutting place of top side wire outlet Cutting place of left side wire outlet Cutting place of right side wire outlet For shielded wiring please refer to the picture below Embedded switch box wiring Wiring hole Wiring through the wall Wall hole and wiring hole Product Features ...

Страница 38: ...address can be set from 0 to 63 by the switch Turn on the unit then the address will be effective Note For light commercial aire conditioner with XYE port it can be also connected to BMS Building Management System If there is any CAC central air conditioner connecting with the central controller at the same time please set the address from largest 63 62 61 since the CAC units could obtain address ...

Страница 39: ...43 4 Outdoor Unit Installation 44 5 Drainage Pipe Installation 45 6 Refrigerant Pipe Installation 47 7 Vacuum Drying and Leakage Checking 49 8 Additional Refrigerant Charge 50 9 Engineering of Insulation 50 10 Engineering of Electrical Wiring 51 11 Panel Installation 52 12 Test Operation 53 Installation ...

Страница 40: ...nt some models 1 Seal ring some models 1 Remote controller Its Frame some models Remote controller 1 Fixing screw for remote controller holder ST2 9 x 10 2 Remote controller holder 1 Dry battery AAA 2 Remote controller illustration 1 EMC Magnetic Ring some models Magnetic ring wrap the electric wires S1 S2 P Q E around the magnetic ring twice 1 Installation Accessory some models Ceiling hook 4 Sus...

Страница 41: ...ew Installation Order L N 1 2 3 4 5 MC MC 6 7 8 Install the indoor unit Install the outdoor unit Install the drainpipe Evacuate the refrigeration system Connect the wires Connect the refrigerant pipes Install the front panel Perform a test run ...

Страница 42: ...m distance between the outdoor unit and walls described in the installation guide does not apply to airtight rooms Be sure to keep the unit unobstructed in at least two of the three directions M N P M N P 30 cm 11 8 from back wall 60 cm 23 6 on right 60 cm 23 6 above 30 cm 11 8 on left 200 cm 78 in front 2 4 Rows of series installation The relations between H A and L are as follows L A L H L 1 2H ...

Страница 43: ... dimensions 2 Body dimensions 3 Decoration panel dimensions 4 Refrigerant piping 5 Suspension bolt 4 6 Ceiling opening dimensions 7 Hanger bracket 8 Ceiling board 2 Drill 4 holes 5cm 2 deep at the ceiling hook positions in the internal ceiling Be sure to hold the drill at a 90 angle to the ceiling 3 Using a hammer insert the ceiling hooks into the pre drilled holes Secure the bolt using the includ...

Страница 44: ...and cause water to leak NOTE FOR NEW HOME INSTALLATION When installing the unit in a new home the ceiling hooks can be embedded in advance Make sure that the hooks do not come loose due to concrete shrinkage After installing the indoor unit fasten the installation paper template onto the unit with bolts M6X12 to determine in advance the dimension and position of the opening on the ceiling Follow t...

Страница 45: ...e installing condensate water pipeline deter mine its route and elevation to avoid intersection with other pipelines and ensure slope is straight 2 Drainage pipe selection The drainage pipe diameter shall not small than the drain hose of indoor unit According to the water flowrate and drainage pipe slope to choose the suitable pipe the water flow rate is decided by the capacity of indoor unit Rela...

Страница 46: ...pe to ensure the condensate water discharge smoothly The air outlet shall face down to prevent dirt enter For Vertical drainage pipe The following table is for reference PVC pipe Reference value of inner diameter of pipe mm Allowable maximum water flowrate l h Remark PVC25 20 220 For branch pipe PVC32 25 410 PVC40 31 730 Could be used for confluence pipe PVC50 40 1440 PVC63 51 2760 PVC75 67 5710 P...

Страница 47: ...t is based on the standard length and the maximum permissive length is based on the system reliability 2 Oil traps If the indoor unit is installed higher than the outdoor unit If oil flows back into the outdoor unit s compressor this might cause liquid compression or deterioration of oil return Oil traps in the rising gas piping can prevent this An oil trap should be installed every 10m 32 8ft of ...

Страница 48: ...between supporters should not be exceed 1 5m 13 Connect the pipe to indoor unit and outdoor unit by using two spanners Be sure to use two spanners and proper torque to fasten the nut too large torque will damage the bellmouthing and too small torque may cause leakage Refer the following table for different pipe connection Pipe Diameter Torque Sketch map N m lb ft 1 4 6 35 15 16 11 11 8 3 8 9 52 25...

Страница 49: ...hours of drying check whether there is leakage source 4 Leakage test After the vacuum degree reaches 755mmHg stop vacuum drying and keep the pressure for 1 hour If the indicator of vacuum gauge does not go up it is qualified If going up it indicates that there is moisture or leak source 7 3 2 Special vacuum drying The special vacuum drying method shall be adopted when 1 Finding moisture during flu...

Страница 50: ... material at the joint pipe shall be inserted into the gap of the insulation material The insulation material at the joint pipe shall be banded to the gap pipe and liquid pipe tightly The linking part should be use glue to paste to gether Be sure not bind the insulation material over tight it may extrude out the air in the material to cause bad 8 Additional Refrigerant Charge After the vacuum dryi...

Страница 51: ...en the insulation material 10 Engineering of Electrical Wiring 1 Highlights of electrical wiring installation All field wiring construction should be finished by qualified electrician Air conditioning equipment should be grounded ac cording to the local electrical regulations Current leakage protection switch should be in stalled Do not connect the power wire to the terminal of signal wire When po...

Страница 52: ...panel to the main board of the unit 11 2 5 Fasten the control box lid with two screws 11 Panel Installation 11 1 11 2 Cassette 650x650 BOX SL 2 Panel Installation 11 2 1 Remove the front grille 1 Slide the 2 grille hooks toward the middle of the decoration panel 2 Hold the grille at a 45 angle lift it up slightly and detach it from the main body 11 2 2 Install the panel 1 Align the indicate on the...

Страница 53: ...r to COOL mode and check the following points Indoor unit Whether the switch on the remote controller works well Whether the buttons on the remote controller works well Whether the air flow louver moves normally Whether the room temperature is adjusted well Whether the indicator lights normally Whether the temporary buttons works well Whether the drainage is normal Whether there is vibration or ab...

Страница 54: ......

Страница 55: ......

Страница 56: ...s Av Manoteras Nº 38 Oficina C303 28050 Madrid España Tel 34 91 6658280 Fax 34 91 6657806 info clivet es CLIVET GmbH Hummelsbütteler Steindamm 84 22851 Norderstedt Germany Tel 49 0 40 32 59 57 0 Fax 49 0 40 32 59 57 194 info de clivet com CLIVET RUSSIA Elektrozavodskaya st 24 office 509 107023 Moscow Russia Tel 74956462009 Fax 74956462009 info ru clivet com CLIVET MIDEAST FZCO Dubai Silicon Oasis ...

Отзывы: