Page 12 - FL-20A Instruction Manual
Model FL-20A Cable Fault Locator
until the conductors are intentionally discharged. For this reason, an
operator using the FL-20A in an open area is required to hold in the
safety buttons on each side of the fault locator. This is a safety precaution
to prevent him or her from touching the test cable while it is charged. In
this situation, Caged Operation is OFF. This is the default setting.
Do not attempt to defeat the safety buttons. Failure to observe
proper safety precautions can result in severe injury or death!
Because it is common practice to use a fault locator in a caged area to
protect workers, the Caged Operation setting can be changed to ON, and
the FL-20A operator can perform a test without pressing in the safety
buttons on each side of the fault locator. To turn ON the Caged Opera-
tion setting, the external interlock on the back of the FL-20A unit must
be connected to the cage door. Press NEXT to access the next screen.
Then press the ON/OFF area of the screen to change Caged Operation
to ON. Press ACCEPT.
Unit of Measure
Test cable lengths may be displayed in feet or meters. The unit of mea-
sure cannot be changed during a test. Press the displayed choice to
toggle between Feet or Meters.
System Information
FL-20A firmware and software version numbers are stored here. During
troubleshooting, you may be asked for this information by a Clinton
technician.
System Errors
System error information is stored here. A Clinton technician may
request that you access this information during troubleshooting if the
yellow or red lights on the back of the FL-20A are flashing.
Set System Defaults
The Set System Defaults RESTORES system defaults. Restoring System
Defaults does not affect calibration.
Set Admin Password
When Lock Settings is ON, a password is required to access the Settings
menu. Reserving global setting access to supervisory personnel prevents
unauthorized individuals from changing test parameters or defeating
safety features. The default password is 1111. To change it, press the
displayed password to access a keypad. Enter a new 4-digit password
and press the check mark/accept button.
After changing the password, turn Locked Settings Menu ON to prevent
unauthorized access to the Settings menu.