Install the J-profiles in the same way as in the 1-piece mounting.
Apply the sealing compound to the wall.
Lift the TUISKU elements in place and mount them to a load-bearing wall
the same way as in 1-piece mounting.
Mount the TUISKU elements together with zinc-plated drill point screws EJOT JT2-6-6.3x25mm.
TUISKU surface mounting
130 mm
Multielement TUISKU side-by-side
We recommend the following screw types or equivalent to mount the J-profile to the wall:
• Wood: TX-20 4.5X40 full thread chipboard screw csk.hd. Zn
• Concrete: Nyloc plug, Sormat NAT 8 (8x40 mm) + TX-20 4.5X40 full thread chipboard screw csk.hd. Zn
• Sandwich: Hexagon head tapping screw DIN 7504K ZN 4.2 x 13 mm drill point NOTE! maximum mounting load 45 kg/m2
• Steel (RHS or equivalent): EJOT JT2-6-6.3 x 25 mm zinc-plated drill point
We recommend the following screw types or equivalent in mounting the TUISKU to the wall:
• Wood: Farmer screw Ruspert 4.8x25-65 mm, RR, sharp point with washer
• Concrete: Concrete screw Fisher FBS 6 x 40/5 mm US or equivalent
• Sandwich: Sandwich panel screw with washer, drill point (4-14 MM) SPA 5.5 x L = panel thickness
• Steel: EJOT JT2-6-6.3 x 25 mm zinc-plated drill point