Installation guide ECO4

Parts of supply air unit ECO4

1.

  Rear part, collar, heating element, electronic part and contacts for 

supply voltage (230V) and for the regulator cabling

2.

 Perforated cover

3.

 Fixing screw for the perforated cover (2 pcs)

4.

 Fixing screw for the rear part (to a wall, 4 pcs)

Installation of supply air unit ECO4 

1.

  Drill holes into the wall for wires and fixing screws (4), using the 

cutout template supplied with the delivery (for the cutout template 
see Appendix 1).

2.

 The minimum distance of the supply air unit from the ceiling is 10 

mm (see Figure 1.1).

3.

 Pull the cover away from the rear part (1).

4.

 Push the collar of the rear part inside the supply air duct and fix the 

rear part to the wall, using four screws (4), Ø max 5 mm).

5.

 Connect the supply cable of the supply air unit (MMJ) and the control 

cable of the regulator (KLMA) to the terminals of the electronic part 
of the supply air unit as shown on Figure 4.

6.

 Check that all the connections are correct. Push the perforated cover 

back onto the rear part and fix it properly using the fixing screws of 
the cover.

Connection

1.

  Connect supply voltage (230V) to terminals N and L of the electronic 

part of the supply air unit as shown on Figure 2.

2.

 Connect the grounding to the separate ground terminal in the supply 

air unit as shown on Figure 2.

3.

 Connect the supply air unit of the RCL ECO series to the regulator by 

means of the KLMA cable as shown on Figure 2. 

4.

 You can activate temperature drop function by connecting terminals 

Z1 and G0 in the regulator as shown on figure 5.  

5.

 When two or more supply air units are controlled with one regulating 

unit, the G pole of the power unit in only one supply air unit is con-
nected. The poles G0 and A2 are again connected from all controlled 
power units. The supply air devices must be connected in the same 
phase in the distribution box.

Note! Connection work may be performed only by a 
person with necessary professional skills.

WARNING! 230V voltage inside the unit.

1

2

3

5

4

NNLL

L

N

GO

G   A2

Z1     G    A2  

G0   A1

24 VAC

230 VAC

ECO

Regulator

ECO

Supply Air Unit

ECO

10A

MMJ 3X1.5

10A

MMJ 3X1.5

KLMA 3X0.8+0.8

KLMA 3X0.8+0.8

1 ECO/room

ECO

ECO

16A

MMJ 3X2.5

KLMA 3X0.8+0.8

KLMA 2X0.8

2 ECOa/room

KLMA 3X0.8+0.8

ECO

REGULATOR

ECO

ECO

REGULATOR

REGULATOR

16A

MMJ 3X2.5

KLMA 3X0.8+0.8

KLMA 2X0.8

KLMA 2X0.8

3 ECOa/room

ECO4 distance from the ceiling

Min. 10 mm

Cabling modes of the ECO heating system

The protective automatic switches for cables must be type C.

Figure 1

Figure 1.2

Figure 2

Figure 3