Use following instruction to connect module on C-Bus with Cat6 cable: 

 

 

Color 

Color Name 

Pin 

C-Bus  

 

Orange/White 

A(DATA+) 

 

Orange 

B(DATA-) 

 

Green/White 

TXD* 

 

Blue 

RXD* 

 

Blue/White 

GND 

 

Green 

GND 

 

Brown/White 

VCC 

 

Brown 

VCC 

* TXD & RXD will be used in direct mode application of module or in case of 

using long cable, for GND & VCC respectively. 

 

 

 

 

Changing Device Mode 

To  connect  capacitive  loads,  the  module  must  be  set  to 

“Capacitive  Protected  Mode”  by 

Pulling up the Mode selector switch. 

 

When the Mode selector switch is positioned up, the module will work only if 220V phase & 
neutral is connected to the module.  If any of these two connections fails, the Channel LEDs 
will illuminate with proper feedbacks but the relays will not work.  

Module 

LED’s

 

Upon connecting the main power, the green Power LED will start flashing. 
The green Status LED flashes any time a valid data packet received to the micro relay.   
In case of receiving invalid data packet in C-Bus connections, the Status LED will turn on for 
5 seconds.  

Before wiring the device, always unplug the main power. 

In case of using inductive loads, apply a snubber as depicted in above diagram. 

 

Follow the diagram below in  order to apply right input/output and connect modules to 
each other. 
 
 

 

Change Device Address 

The device address can be set from 2 to 31 by switches no. 1 to 5 of dip-switch (address selector 
switches). Before changing address the main power must be disconnected. The address must be 
defined in binary. 

For instance to set the address to “21” the address selector switches must be 

as bellow: 

 

 Never set the address to 0 or 1 (1 is reserved for Climax RS-232 GatewayPro). 

 Before adding a new module on the C-Bus, ensure the previous module has a valid address          

and is working properly. Avoid repetitive address allocation. 

 

Operating Control Inputs 

Each  channel  can  be  toggled  by  connecting/disconnecting  COM  &  corresponding  input  on 

control pins. 

 