Tranquility Aluminum Tube Cased Coil (TAC)
R e v. : A u g u s t 2 1 , 2 0 1 8
8
G e o t h e r m a l H e a t i n g a n d C o o l i n g
Installation
The Tranquility Cased Coils are designed for upflow, horizon-
tal, and downflow applications. The coils have a dry nitrogen
holding charge and are equipped with brazing stub refriger-
ant connections for easy installation.
The installer should read the installation manual supplied
with the compressor section for refrigerant line set sizing,
connection procedure, and other important information per-
taining to the system installation.
The installer should:
1. Make sure that the air delivery of the furnace is adequate
enough to handle the recommended CFM and allow for
pressure drop across the air coil, filter, and duct work.
2. Where precise forming of refrigerant lines is required, a
copper tubing bender is recommended for small diameter
tubing. One should avoid sharp bends and contact of the
refrigerant lines with metal surfaces.
3. Refrigerant lines should be protected where they pass
through the raw edges of holes.
4. Coil must be level or slightly pitched toward drain for
proper condensate drainage.
5. Seal the openings into the cabinet to reduce risk of con-
densate blow off from the coil.
The installer should:
1. Disconnect all electrical power to the furnace.
2. For the install of an cased coil, it might be necessary to
fabricate a plate to adapt the coil’s cabinet to the furnace
or air handler air discharge opening.
3. Install the cabinet and level or slightly pitch it as needed to
allow proper condensate drainage.
4. Seal the enclosure as required minimizing air leakage.
5. Connect the refrigerant lines as outlined in the Refrigerant
Lines section.
Cased Coil Installation
�
WARNING!
�
WARNING!
Electric furnaces may be connected to
more than one supply circuit.