Charging
5.7 CHARGING CHARTS
5.0 SYSTEM START-UP & REFRIGERANT CHARGING
Split System Air Conditioner 20 Tons
System Charge Chart - Refrigerant 410A
Basic System Charge With 0 Feet Of Tubing =650 oz
Add Additional Amount As Shown In Table Below
92-108042-01
Cooling Instructions
INSTRUCTIONS:
1. Connect Pressure Gauges To Vapor And Liquid Ports At Outdoor Unit.
2. Measure Air Temperature To The Unit (Outdoor Dry Bulb Ambient).
3. Place An “X” On The Chart Where The Vapor And Liquid Pressure Cross.
4. If “X” Is Below Outdoor Temperature Line, Add Charge And Repeat 3.
5. If “X” Is Above Indoor Temperature Line, Recover Charge And Repeat 3.
6. Pressures Are Ref. Only -Final Charge Verification To Be Based On “Design
Subcooling” Note At The Top Of The Cooling Chart.
Caution: Return Air Temperature Must Be Between 70° & 75° Before Final
Refrigerant Check.
1/2 [12.7]
1.06 [30.0] .04 [1.13]
5/8 [15.88]
1.65 [46.7] .07 [1.98]
3/4 [19.05]
2.46 [69.7] .10 [2.83]
7/8 [22.23]
3.28 [92.9] .13 [3.68]
1-1/8 [28.58]
.22 [6.23]
1-3/8 [34.93]
.34 [9.63]
1-5/8 [41.28]
.48 [13.60]
2-1/8 [53.98]
.84 [23.81]
Quantities based on 110°F liquid and 45°F vapor.
Required Ounces R-410A Charge Per Foot of Tubing
Tube Size O.D. in. [mm]
Liquid Tube
oz [g]
Vapor Tube
oz [g]
225
275
325
375
425
475
525
575
625
100
120
140
160
180
200
220
Pr
es
su
re
a
t l
iq
ui
d
se
rv
ic
e
po
rt
-
PSI
G
Pressure at vapor service port - PSIG
COOLING
Design Subcooling @ 95°F Ambient = 19°F (At Service Valve)