![ClimaCheck BGS2 Скачать руководство пользователя страница 6](http://html.mh-extra.com/html/climacheck/bgs2/bgs2_manual_2624465006.webp)
ClimaCheck GSM Modem Manual – 2015-02-26 6(22)
In older versions of the PA Pro standard configuration the
Phone number to ISP
field is blank. If
that is the case enter
*99***1#
and click
Update
.
You will need to press
Restart
to enable the new settings, but you only need to do this once after
finishing all configuration. You can also restart your PA Pro by turning on and off the power.
APN for a number of operators:
NextM2M
fixedipaccess (Standard for ClimaCheck SIM)
Telia
online.telia.se
Maingate
maingate.telia.se
Maingate VPN
maingatelan.telia.se
Maingate Roaming
apn.maingate.se
Telenor
internet.telenor.se
O2 UK
mobile.o2.co.uk
3.3
Changing the Database Sample Interval
When using your PA Pro connected directly to a laptop five seconds between each sampling of data
is the standard value. When connecting by GPRS the sample rate is set in the logger and usually to
a lower value not to cause an unnecessary high data traffic cost. The settings for the internal
logger and data transfer are independent.
Choose
Settings -> Advanced -> Databases -> DB1 Short Time
.
Set
Time base 1
to the sample interval you want when the compressor is not running. We
recommend
5 minutes
for most situations.
Set
Time base 2
to the sample interval you want when the compressor is running. We
recommend
1 minute
for most situations.
Click
Update
to confirm your changes.
Figure 3
In older versions of the PA Pro standard configuration there is no option to set a different sample
interval for when the compressor is not running. In this case just use the standard
Time base
setting.
3.4
Changing Database UDP settings
The
Database UDP
section contains information that allows the PA Pro to connect to our server.
Choose
Settings -> Advanced -> Database UDP
.
Set
ID
to the identifier for your account. It is provided to you by ClimaCheck or one of our
partners and always contains
six letters or digits
.