background image

 

 

REV. FEBRUARY 19th 2014 

CLIMA-FLEX S.A. DE C.V.

 

1. 

GENERAL DESCRIPTION 

GENERAL DESCRIPTION 

 

CLIMAFLEX 

chiller units are built with control and design in 

mind,  assembled  with  technically  specialized  control 
software. Some of our features are in house production of all 
piping  and  wiring,  scroll  type  compressors,  new  generation 
evaporators,  air  cooled  condensers,  optional  hydraulic 
components,  and  several  safety  and  security  protections. 
Our  units  are  ecofriendly  and  operate  with  R-410A 
refrigerant.

 

ELECTRICAL COMPONENTS 

 

All  units  are  equipped  with  a  control  panel,  security  anti-
theft devices, internal and external overheating protection, 
compressor  drive  protection,  flow  protection,  freezing 
protection  and  electrical  failure  protection.  The  control 
panel has LED operation indicating lights.

 

EQUIPMENT 

 

Fully Factory assembled, and individually run tested with all 
required piping, wiring, and controls for operation. 

 

HYDRAULIC COMPONENTS (OPTIONAL) 

 

Water Pump 

 

The  drive  in  the  water  pump  is  TEFC  (Totally  Enclosed 
Fan  Cooled)  and  has  anti-corrosive  coating  on  the 
housing.

 

MODULE 

 

Steel base, anti-corrosive painted steel panels. Easy Access 
for maintenance without compromising the unit´s stability. 

 

CONTROL 

 

The  control  unit  allows  the  connection  of  the  unit  to  the 
INTERNET,  and  allows  the  user  to  visualize  all  the  unit

’s 

operating information, such as variable graphics, tendencies 
cycle time, diagnosis of components, alarms, etc. Access to 
this  information  renders  a  more  efficient  operation  and 
system control. 
 
 
 

 
 

COMPRESSORS 

 

Two stage Scroll type hermetic compressors.

 

CONDENSERS 

 

High  efficiency  microchannel  with  optional  anti-corrosive 
coating.

 

EVAPORATORS 

 

Compact  Plate  Heat  exchangers  with  thermally  isolated 
hydraulic refrigerant pipes and connections.

 

FANS 

 

Low vibration and noise Axial Fans. 

 

COMPONENTS 

 

REFRIGERATION CONTROLS 

 

The  units  are  equipped  with  solenoid  valves,  expansion 
valves, dehydrator, and service valves.

 

 
 

 

 

Содержание CLIV SERIES

Страница 1: ...REV FEBRUARY 19th 2014 CLIMA FLEX S A DE C V CLIV SERIES Air cooled ...

Страница 2: ...REV FEBRUARY 19th 2014 CLIMA FLEX S A DE C V Installation Manual CLIV Series ...

Страница 3: ...h all required piping wiring and controls for operation HYDRAULIC COMPONENTS OPTIONAL Water Pump The drive in the water pump is TEFC Totally Enclosed Fan Cooled and has anti corrosive coating on the housing MODULE Steel base anti corrosive painted steel panels Easy Access for maintenance without compromising the unit s stability CONTROL The control unit allows the connection of the unit to the INT...

Страница 4: ...esired temperature in a precise and fast manner with high efficiency and minimum energy consumption CLIV CLIMAFLEX unit capacity ranges from 3 to 5 Tons OPERATION CLIV CLIMAFLEX units have reduced vibration levels making them virtually silent The overall design allows for easy fast and low price installation QUALITY Each unit is carefully manufactured and individually tested under strict internati...

Страница 5: ...REV FEBRUARY 19th 2014 CLIMA FLEX S A DE C V 1 2 CLIMA FLEX INSTALLATION DIAGRAM ...

Страница 6: ...CLIV ACC 60 000 A 3 S 1 2 3 4 5 6 1 SERIE CLIV Air cooled bank type module 2 TYPE ACC Air Cooled Cooling Only ACH Air Cooled heat pump 3 NOMINAL CAPACITY 036 36 000 BTU HR 060 60 000 BTU HR 4 FAN A Axial 5 VOLTAGE 3 220 3 60 2 440 3 60 6 COMPRESSORS S Two Stage ...

Страница 7: ...Operating Current Amps 1 80 1 80 1 80 1 80 Power KW 0 20 0 20 0 20 0 20 Power HP 1 6 1 6 1 6 1 6 PLATE HEAT EXCHANGER Water input temperature ºC ºF 12 7 55 12 7 55 12 7 55 12 7 55 Water output temperature ºC ºF 7 2 45 7 2 45 7 2 45 7 2 45 DIMENSIONS Length cm in 109 70 43 19 109 70 43 19 109 70 43 19 109 70 43 19 Depth cm in 68 73 27 06 68 73 27 06 68 73 27 06 68 73 27 06 Height cm in 103 13 40 60...

Страница 8: ... COMPRESSOR FAN MIN MAX LRA OPERATING AMPERAGE 1 RLA CANT RLA HP CLIV ACC 036 A3S 220 3 60 8 20 13 19 70 12 90 73 7 50 12 9 1 2 77 1 1 4 CLIV ACC 061 A3S 220 3 60 8 29 18 28 50 17 80 110 11 40 18 4 1 2 77 1 1 4 MCA MAXIMUM CURRENT AMPACITY MOP MAXIMUM OPERATIONAL AMPACITY LRA LOCKED ROTOR AMPACITY AMP OP AMPACITY OF OPERATION RLA RATED LOAD AMPACITY HP HORSE POWER ...

Страница 9: ...REV FEBRUARY 19th 2014 CLIMA FLEX S A DE C V 5 ELECTRICAL DIAGRAM CONTROL DIAGRAMCLIV ACC 036 A3S CLIV ACC 061 A3S ...

Страница 10: ...REV FEBRUARY 19th 2014 CLIMA FLEX S A DE C V POWER DIAGRAM CLIV ACC 036 A3S CLIV ACC 061 A3S ...

Страница 11: ...REV FEBRUARY 19th 2014 CLIMA FLEX S A DE C V 6 DIMENSIONS CLIV ACC 036 A3S CLIV ACH 036 A3S CLIV ACC 061 A3S CLIV ACH 061 A3S ...

Страница 12: ...32 2 C 95 F 35 C 100 F 37 7 C 105 F 40 5 C MODEL BTU HR KW EER BTU HR KW EER BTU HR KW EER BTU HR KW EER BTU HR KW EER CLIV ACC 036 A3S 33 000 2 99 11 04 31 900 3 12 10 22 30 800 3 27 9 42 29 600 3 42 8 65 28 400 3 59 7 91 CLIV ACC 061 A3S 55 300 4 23 13 07 53 600 4 44 12 07 51 900 4 66 11 14 50 100 4 90 10 22 48 200 5 17 9 32 ...

Страница 13: ...V Units are designed to be installed in interiors It is necessary that the unit has air venting and a free air intake see Fig 1 to allow for good air circulation and allow access for maintenance For fully functioning CLIV units only require the connection with the hydraulic local net and power supply connection in accordance with technical data sheet Note For optimal operation machinery room shoul...

Страница 14: ...at air intake is not obstructed and has the required space suggested on Fig 1 2 HYDRAULIC CIRCUIT INSPECTION Water connections are NPT type inner thread to identify the connection diameter see unit s data sheet The installation of a water filter is necessary on all hydraulic circuits in order to avoid solid particles in it which must be installed on the return side of the circuit and cleaned once ...

Страница 15: ...nd band tension Check that air intake is not obstructed and has the required space suggested on Fig 1 1 HYDRAULIC CIRCUIT INSPECTION Water connections are NPT type inner thread to identify the connection diameter see unit s data sheet The installation of a water filter is necessary on all hydraulic circuits in order to avoid solid particles in it which must be installed on the return side of the c...

Страница 16: ... monitor control Motor Saver to be adjusted to supply the correct power voltage for the unit Note The unit s control panel has a ventilation duct and it must not be obstructed in any manner The unbalance percentage of electrical supply should be calculated with the following formula and adjusted on the UNBALANCE TRIP knob UNBALANCE PORCENTAGE MAXIM AVERAGE DEVIATION AVERAGE X 100 Note CLIMA FLEX u...

Страница 17: ...finishing the inspection of the previous installation points and making sure all the unit s items are correct the unit may be started 1 UNIT CONTROL Set the UNIT CONTROL switch on the ON position Fig 2 to energize the control panel with 24 Volts After energizing the controller wait five minutes for the unit to be on line and ready 2 ON OFF Operation sequence will initiate by checking all security ...

Страница 18: ...afterwards set the APG2 switch also to the ON position this will enable the compressors start cycle Note The APG4 switch Fig 3 selects the unit s operating mode whether is it cooling only or heat pump If you wish to operate the unit as heat pump turn this switch to ON Fig 2CoolingOnlyMode Compressor 24V Reset ...

Страница 19: ...REV FEBRUARY 19th 2014 CLIMA FLEX S A DE C V Operation Manual CLIV Series ...

Страница 20: ...OMECLATURE Fig 1 No1 On Off COMPRESSOR AND FAN FIRST STAGE No3 On OFF Pump No4 On Off SECOND STAGE B1 Return Sensor B2 Supply Sensor B3 Freezing Sensor ID1 Motor Saver ID2 Flow Sensor ID3 High pressure Sensor ID4 Low pressure Sensor ID5 ON OFF Remote ...

Страница 21: ...for this panel version the present symbols are indicated on the display and on the keyboard Fig 2 2 1 DISPLAY SIMBOLOGY Symbol Color Meaning Reference refrigerant circuit LED On Blinking LED 1 2 amber Compressor 1 or 2 ON On Demand 1 3 4 amber Compressor 1 or 4 ON On Demand 2 A amber At least one compressor is ON 1 2 B amber Pump Fan running On Demand 1 2 C amber Condenser Fan ON 1 2 D amber Defro...

Страница 22: ...ressure reduces the alarm will reset automatically LP1 Low Pressure Alarm The unit is operating on low pressure as the pressure rises the alarm will reset automatically TP General Thermal switch Phase Alarm with voltage problems Motor Saver sends a signal to open the switch it will automatically reset once the problem is corrected ...

Страница 23: ... E3 Alarm broken freezing sensor Sensor failure alarms B1 B2 or B3 respectively this is due to a false contact or malfunction of the sensor It is necessary to troubleshoot the connection or change the sensor 3 1 TEMPERATURE DISPLAY To access the temperature on the display navigate using the Up and Down keys Navigation Keys The temperature set by default is the temperature B02 injection Using the n...

Страница 24: ...REV FEBRUARY 19th 2014 CLIMA FLEX S A DE C V Maintenance Manual CLIV Series ...

Страница 25: ...nd starters on the electrical panel Check amperage on all motors and compare them to plate values Physically check for false contacts Verify status of all electrical protections to be under the manufacturer specifications Clean the electrical panels 1 3 PHYSICAL INSPECTION Condenser cleaning with pressurized clean water interval depends on ambient conditions Check refrigerant load 3 months period ...

Страница 26: ...ed and qualified personnel equipped with the proper tools COOLING MODE Nominal Capacity BTU hr Rated Capacity BTU hr EER BTU W h IPLV EER COPR 61 000 51 900 11 51 15 78 3 37 HEATING MODE Heating Capacity BTU hr Power Consumption kW COPH Leaving water temperature F 64 562 4 70 4 03 110 UNIT DATA Refrigerant Type Refrigerant Weight lbs Sound Level Db Net Weight lbs Operation Weight lbs Controller To...

Страница 27: ...5 Parque Industrial Logistico Delegacion La Pila San Luis Potosí México ZIP Code 78422 Phone 52 444 161 5043 Facebook clima flex climaflexMexico www clima flex com CLIV SERIES CLIV ACH 061 A3S HEAT PUMP Mini Chiller Air Cooled Axial Fan ...

Отзывы: