CLIFC VARIABLE - INSTALLATION, OPERATION AND MAINTENANCE MANUAL

Maintenance (Cont’d.)

FANS

Inspection of the fan assemblies (comprising the impellor and the motor) should be undertaken to ascertain 

whether any overheating of the motor is occurring, and to check that the fan impeller is free running and 

has not sustained any damage.

The fan assembly should be cleaned regularly, as any excessive build-up of dust or debris may cause the impellor 

to fall out of balance, or the motor to overheat.

The impellor and motor should only be cleaned with a soft dry brush to remove dust deposits. The fixings holding 

the fan motor to the fan scroll should be checked and tightened if necessary.

In addition, the fixing screws holding the fan scroll to the main body of the equipment should also be checked and 

tightened as required

These fixings must be secure before checking the fan bearings. Standard fan bearings are “sealed for life”, therefore 

no specific maintenance is possible. In normal service, the fans have an anticipated life of 40,000 hours.

However, the condition of the bearings should be checked and assessed at regular intervals as follows:

•  The fan impellor should be rotated manually to detect any roughness or flat spots in the bearings.

•  Gentle lateral pressure should be applied back and forth on the impellor to detect any excessive movement or 

play in the bearings.

If any roughness, flat spots or excessive movement is found, then the fans should be replaced.

INTERNAL AND EXTERNAL SURFACE

All nuts, bolts and fixings should be checked for tightness. The general condition of all components and 

the equipment overall should be checked.

The steel internal and external surfaces of the equipment should be regularly checked for scratches, corrosion, or 

for peeling of painted surfaces.

If found, thoroughly clean affected areas with a wire brush, apply a coat of zinc rich primer or similar, and re-touch 

with suitable finishing paint.

The insulating materials should be checked for condition and security. If the insulation shows signs of powdering 

then it must be replaced. Insulation which is loose or peeling off should be made secure.

To replace insulation, proceed as follows:

Ensure that sufficient new insulation material with Class “O” fire resistance is available.

2. Peel off the existing affected insulation from the equipment casing.

3. Remove any old glue residues or residual foam.

4. Clean the area using suitable solvent cleaner such as ISO Propyl alcohol.

5. Position ETL / UL rated glue on the equipment casing, and press the new insulation into place. Let it cure and dry

IMPORTANT: ETL / UL 

rated glue

 MUST 

be used for the unit to maintain its ETL rating.

Содержание CliFC 1000

Страница 1: ...INSTALLATION OPERATION AND OPERATION MANUAL CLIFC VARIABLE SERIE HORIZONTAL VARIABLE FAN COIL 400 600 800 1 000 1 200 1 300 1 600 2 000 CFM ...

Страница 2: ...2 CLIMA FLEX CLIFC VARIABLE INSTALLATION OPERATION AND MAINTENANCE MANUAL THIS PAGE INTENTIONALLY LEFT BLANK ...

Страница 3: ... INSTALLATION OPERATION AND MAINTENANCE MANUAL Content Nomenclature 4 Standard features 5 Components 6 Operation 7 Ubicación Instalación 8 Performance sound data 9 Dimentional data 10 Electrical data 18 Maintenance 19 Control 23 ...

Страница 4: ...00 800 CFM 1000 1 000 CFM 1300 1 300 CFM High Static 1200 1 200 CFM 1600 1 600 CFM 2000 2 000 CFM Voltage 0 115 127 1 60 Cooling rows 3 3 rows 4 4 rows 6 6 rows Heating rows 0 0 rows 1 1 row 2 2 rows Conexión hidráulica R Right L Left Fan type F EC Fan Corrosion protection E Coil protection 0 N A Plenum P With plenum N N A Filter D Disposable N N A Control 1 VLD 2 Microset 0 N A ...

Страница 5: ...g in the entire range of the fan motor from 1 to 100 which allows it to adjust very precisely to the demand at any given time Modulating its operation and saving electrical energy It reduces moisture significantly during normal operation even when the unit is in standby mode By reducing the humidity a more pleasant atmosphere is created for the users and the useful life of the elements of the room...

Страница 6: ...ed coils are manufactured and tested in house Centrifugal fans Sturdy reliable and silent Electronic 2 or 3 way valve With smart actuator to control water flow to the coil very precisely to maintain the injection temperature Programmable digital thermostat With 5 daily time schedules and humidity sensor Aesthetic design easy to use and multiple programming options Temperature sensors Analog readin...

Страница 7: ...s the speed of the fan to meet the changes of the demand The logic of operation starts from the premise that once the Set Point is reached the demand is lower and the system is not required to operate at a higher capacity When the demand either cooling or heating begins to decrease the system decreases the electricity consumption because it decreases the energy delivered to the fan The unit become...

Страница 8: ...A FLEX CLIFC VARIABLE INSTALLATION OPERATION AND MAINTENANCE MANUAL Ubicación Instalación Installation detail 500 mm Service clearance Support structure Roof Suspension rod Nut Sealing washer Unit Return Air ...

Страница 9: ...6 2 2 51 59 135 1200 I Variable 2 115 1 50 60 2330 310 6 2 2 51 59 135 1600 D Variable 2 115 1 50 60 2330 310 6 2 3 59 59 145 1600 I Variable 2 115 1 50 60 2330 310 6 2 3 59 59 145 2000 D Variable 2 115 1 50 60 2330 310 6 2 5 59 150 Air Return Water Capacity Air Injection Modelo DB F WB F Ent F Sal F Total BTU h Sensible Btu h DB F WB F 400 80 67 45 55 13540 9370 55 75 54 51 400 80 67 45 55 13540 ...

Страница 10: ...ated 2 All plenums include throw away filter 3 Filter has separate filter access panel for easier service 4 All dimensions in inches C O I L PLENUM PLENUM Drain pan IN OUT FILTER Filter Fan COIL Pipe fastener Plenum section D 12 11 1 4 F 8 3 8 7 3 8 3 8 C R1 8 10 3 4 1 1 2 6 3 4 1 10 1 4 11 8 1 4 11 1 4 F 8 3 4 E 1 A B Acces valve for purge RETURN SUPPLY 1 Male drain connection Ø1 Electrical conne...

Страница 11: ... insulated 2 All plenums include throw away filter 3 Filter has separate filter access panel for easier service 4 All dimensions in inches C O I L PLENUM PLENUM Drain pan IN OUT FILTER Filter Fan COIL Pipe fastener Plenum section 6 3 4 1 10 1 4 Access valve for purge RETURN SUPPLY Male drain connection Ø1 Electrical connection Filter bottom access 11 8 9 3 4 10 3 4 C 8 3 8 7 3 8 3 8 B 11 1 4 12 F ...

Страница 12: ...ted 2 All plenums include throw away filter 3 Filter has separate filter access panel for easier service 4 All dimensions in inches C O I L PLENUM PLENUM Drain pan IN OUT FILTER Filter Fan COIL Pipe fastener Plenum section Access valve for deposition RETURN INJECTION Male drain connection Ø1 Electrical connection Filter bottom access B F 11 1 4 13 10 3 4 12 10 1 4 1 1 1 2 A 1 C 8 3 8 7 3 8 R1 8 3 ...

Страница 13: ...lenums are insulated 2 All plenums include throw away filter 3 Filter has separate filter access panel for easier service 4 All dimensions in inches C O I L PLENUM PLENUM IN OUT COIL Plenum section D 17 1 2 F 11 1 4 3 8 B A 10 3 4 14 3 8 1 1 2 1 G C 12 1 4 7 3 8 R1 8 F 11 1 4 E E 10 1 4 1 16 1 2 1 11 7 8 9 5 8 6 3 4 Fan Filter Drain pan Male drain connection Ø1 Filter bottom access Pipe fastener S...

Страница 14: ...ated 2 All plenums include throw away filter 3 Filter has separate filter access panel for easier service 4 All dimensions in inches C O I L PLENUM PLENUM IN OUT COIL Plenum section TOP VIEW SUPPLY VIEW LEFT VIEW RIGHT VIEW RETURN VIEW Connection Ø1 D F 17 1 2 11 1 4 B 3 8 R1 8 7 3 8 12 1 4 G 13 3 4 14 3 8 1 1 2 A 1 8 1 10 1 4 16 1 2 1 11 7 8 9 3 4 11 1 4 F Fan Filter Drain pan Male drain connecti...

Страница 15: ...2 All plenums include throw away filter 3 Filter has separate filter access panel for easier service 4 All dimensions in inches C O I L PLENUM PLENUM IN OUT COIL Plenum section TOP VIEW SUPPLY VIEW LEFT VIEW RIGHT VIEW RETURN VIEW Connection Ø1 F 11 1 8 B 3 8 R1 8 7 3 8 17 3 4 19 11 1 4 F Fan Filter Drain pan Male drain connection Ø1 Filter bottom access Pipe fastener Filter C RETURN SUPPLY Electr...

Страница 16: ...are insulated 2 All plenums include throw away filter 3 Filter has separate filter access panel for easier service 4 All dimensions in inches C O I L PLENUM PLENUM IN OUT COIL Plenum section TOP VIEW SUPPLY VIEW LEFT VIEW RIGHT VIEW RETURN VIEW Fan bottom access Filter bottom access Fan Male drain connection Ø1 Drain pan Filter Connection Ø1 Pipe fastener D 23 11 1 4 F C 7 3 8 17 3 4 B 3 8 R1 8 F ...

Страница 17: ...are insulated 2 All plenums include throw away filter 3 Filter has separate filter access panel for easier service 4 All dimensions in inches C O I L PLENUM PLENUM IN OUT COIL Plenum section TOP VIEW SUPPLY VIEW LEFT VIEW RIGHT VIEW RETURN VIEW 17 3 4 19 E 1 10 1 4 22 1 15 11 7 8 F 11 1 4 Fan bottom access Filter bottom access Fan Male drain connection Ø1 Drain pan E D 17 3 4 7 3 8 3 8 R1 8 C F 11...

Страница 18: ...18 CLIMA FLEX CLIFC VARIABLE INSTALLATION OPERATION AND MAINTENANCE MANUAL Electrical data ALL MODELS ...

Страница 19: ...ustic output may also be adversely affected by dirty filters The length of time between cleaning of filters is dependent upon the air condition A three month cycle is normal however more frequent maintenance may be required in some cases There is one air filter fitted to the equipment in the inlet air path upstream of the heat exchange coil The filter may be slid out to either side of the unit Alt...

Страница 20: ...eaders and return bends To inspect both faces of the coil the fan access panels and air filter should be removed Maintenance is performed as follows Superficial dust or debris can be removed from the surface by gently brushing with a soft long haired brush Debris can then be vacuumed from the surfaces and other Areas Remove stubborn deposits or biological contaminants by careful application of a d...

Страница 21: ...ts in the bearings Gentle lateral pressure should be applied back and forth on the impellor to detect any excessive movement or play in the bearings If any roughness flat spots or excessive movement is found then the fans should be replaced INTERNAL AND EXTERNAL SURFACE All nuts bolts and fixings should be checked for tightness The general condition of all components and the equipment overall shou...

Страница 22: ...ng persistently this condition must be investigated immediately and the equipment must not be returned to service until the problem has been found and rectified MAINTENANCE PLAN In order to maximize the useful life of the equipment and keep it operating in good order the maintenance checks and tasks detailed in these instructions should be performed as part of a regular and routine service schedul...

Страница 23: ...figuration Menu 1 Press SYSTEM the text at the bottom squares will clear Exit Configuration Menu 3 Press DONE to return to the normal operation menu Turn the unit OFF Press OFF make sure that OFF is blinking and press DONE 2 Press AND HOLD the middle square for five 5 seconds The menu will change to display the configuration variables Set Point Selection Use the HIGHER or LOWER arrows to define Se...

Страница 24: ...ect the desired motor percentage value Available range of operation is 100 to 0 of the motor power curve Press DONE to return to the normal operation menu High Temperature Limit To adjust the fan highest speed available Use the left arrows to navigate to the variable FU Using the right arrows select the desired value Available range of operation is 100 to 0 of the motor power curve Press DONE to r...

Страница 25: ...CLIMA FLEX 25 CLIFC VARIABLE INSTALLATION OPERATION AND MAINTENANCE MANUAL THIS PAGE INTENTIONALLY LEFT BLANK ...

Страница 26: ...CLIFC Horizontal Variable Fan Coil Av Central No 285 Parque Logístico Deleg La Pila San Luis Potosí C P 78422 More info 444 161 50 43 info clima flex com Lada sin costo 01 800 890 59 17 ...

Отзывы: