Installation:
This CFLLED Surface Mount Non-maintained Emergency can be installed on PLASTER or solid block
walls.
1.
Take off the front external cover by inserting a flat blade screwdriver into the slots along the
bottom edge of the fitting.
2.
Mark the mounting hole positions on the wall and drill fixing holes
3.
Using the appropriate fixing hardware for the wall surface fix the CFLLED to the wall.
4.
If hard wiring, remove the flex and plug after removing the internal cover plate over the terminal
block.
5.
If hard wiring terminates the 240V, 50Hz supply to the terminals marked A, N & E. The cable
entry hole through the back of the unit is shown in the image below. Install the internal cover
plate over the top of the terminal block.
6.
Re-install the External Front Cover by pushing it back into place until it clicks in top and bottom.
7.
If using the flex and plug, plug it into a suitable socket (240V, 50Hz).
8.
Adjust the LED heads into position. Two screws are provided for each head to move them into
position. The front screw adjusts the L/R position (roll) and the side screw adjusts the U/D (tilt)
position. There is a standard positioning marker on the body representing a 30° roll out and 30°
tilt down
– this is the position that provides the maximum square area coverage when wall
mounted at 3m
9.
If the CTP capabilities are activated, please affix the CTP status label to a visible surface and
Four Segment Marking on the product will include an ‘’F’’ in third segment block
Networking:
When installing the product on a monitored network, (ZONEWORKS, DATA, HIVE, DALI) simply insert
the relevant Smart Node PCA.
Dimensions:
Testing:
When the CFLLED unit is connected to the un-switched active, it must be allowed to charge the battery
for at least 24 hours. The emergency lamp only illuminates during a power fail. Conduct the following tests:
•
The emergency lamp must illuminate for at least 2 hours after disconnection from the mains. The
results of all tests are required to be recorded in a service logbook, which is to be kept on-site at all
times. If the unit fails to illuminate for the requisite time, remedial action must be taken to repair the
situation and once completed, the unit must pass a subsequent test.
•
Press and hold Test Button or switch Off Mains Supply, check that the emergency lamp is On.
•
Release the Test Button or Switch On Mains Supply, check that the emergency lamp is Off (Non-
maintained operation).
Trouble Shooting:
Below are a list of common problems and their possible causes.
Fault:
The Green LED Test Switch indicator is not illuminated.
Check: A.C. is connected and is turned on.
Battery is connected
Test Switch for damage.
Fault:
Lamp does not illuminate in emergency mode.
Check: A.C. is connected.
Lamp is correctly inserted.
Battery is connected
Fault:
Lamp illuminates in emergency mode, but only stays on for a short period.
Check:
Battery has been allowed to charge for at least 24 hours.
Battery for damage.
Rated Emergency Lumen Output in accordance with AS2293.1, not applicable
for
–TH (theatre) version (refer to spacing tables for installation positions):
Refer to the Technical Label for classification information.
Caution:
On many building sites, power circuits may be cut off in an uncontrolled and repetitive basis during
construction. As a result, any Exit & Emergency Units, on these circuits, will have their batteries
discharged or “cycled”. The battery in this fitting has been selected to give excellent long-life
performance in a controlled AS2293 testing environment. Excessive battery cycling will reduce through-
life performance and may lead to premature battery failure. Battery warranty claims, as a result of such
abuse, are specifically EXCLUDED from Clevertronics warranty terms.
Warranty:
For Product Warranty information and Terms and Conditions of Sales please refer to our website
http://clevertronics.com.au/terms-conditions-sale-australia-nz/