Installation:

 

The  LP  Ultrablade  Pro  LED  Exit  (CUBPRO)  is  a  recessed  ceiling  mount  fitting.  The  CUBPRO  can  be 
attached directly to any solid surface, or to a ceiling tile with the integrated clamping mechanisms. The 
CUBPRO comes with an attached Flex and Plug. Please follow the steps below to install the CUBPRO 
Exit: 

 

If replacing an Ultrablade, an Ultrablade to Ultrablade Pro adapter 2740054 (sold separately) 
is required) 

 

Create a cut-out (350mm x 48mm) in the mounting surface.  

 

Route the power cord to the mains connection and connect the 240VAC supply. 

 

Insert the CUBPRO into the ceiling cavity tighten the (4) clamping screws.  

 

The standard maximum ceiling thickness is 18mm. Trim Clamp as per below image for ceiling 
thickness up to 25mm.  

 

Alternately, fix the CUBPRO to a solid surface using (4) screws through the surface material. 

 

Install the cover plate. 

 

Apply power to the fitting and test. 

 

If the CTP capabilities are activated, please affix the CTP status label to a visible surface and Four 
Segment Marking on 

the product will include an ‘’F’’ in third segment block. 

Dimensions: 

 

Changing EXIT Legend Inserts

:

  

The Ultrablade Pro Exit comes with an assortment of standard legends.  
1. 

To remove the legend, grasp the centre of the bottom trim piece and pull down slightly to 
expose the legend edge. See photo. 

2. 

Grasp the bottom edge of the legend and slide the existing legend out of the blade, while 
working the edges out along the sides. 

3. 

Slide the new legend into the blade, ensuring to fit the edges into the sides then slide the 
legend to the top of the blade. Insert one bottom corner then the other. Slide the legend down 
into the bottom trim. 

Testing:

 

Once connected to the 240V mains supply, the unit must be allowed to charge the battery for at least 24 
hours. Conduct the following tests: 

 

For the first test, the emergency lamp must remain illuminated for at least 2 hours after 
disconnection from the mains supply. 

 

Subsequent tests require the unit to illuminate for at least 90 minutes. The results of all tests are 
required to be recorded in a service logbook, which is to be kept on-site at all times. If the unit fails 
to remain illuminated for the requisite time, remedial action must be taken to repair the situation 
and once completed, the unit must pass a subsequent test. For more specific information, please 
refer to the current edition of the AS 2293.3 Standard. 

Ultrablade Maintenance: 

 

LED Lamp Replacement:

 

 

Use only the LED Strip recommended in 
the Spares Parts list of this instruction. 

 

Disconnect battery from LED driver pack 
and cut cable tie to remove. 

 

Disconnect the signal cable from LED strip, 
loosen screw and remove the mains driver 
pack. 

 

Remove 4 self-tapping screws and unclip 
the LED strip. 

 

Install the new LED strip following the 
above procedure in reverse.

 

 

Battery Replacement:

 

 

Use only the battery recommended in the 
Spares List on this instruction. 

 

Remove the cable ties holding the battery, 
un-plug the lead from the battery connector 
remove the old battery.  

 

Plug the new battery into the battery 
connector.  

 

Secure the battery using suitable cable ties 

 

Trouble Shooting: 

Below are a list of common problems and their 
possible causes. 

 
Fault:  

The Green LED Test Switch 
indicator is not illuminated.

 

Check:   A.C. is connected and is turned on. 
 

Battery is connected 
Test Switch for damage. 
 

Fault:  

Lamp does not illuminate in 
emergency mode. 

 

Check:   A.C. is connected. 
 

Lamp is correctly inserted. 

 

Battery is connected 

 

Fault:  

Lamp illuminates in emergency 
mode, but only stays on for a short 
period. 

Check: 

Battery has been allowed to charge for 
at least 24 hours. 

 

Battery for damage.

 

 

Rated Emergency Lumen Output in accordance with AS2293.1, not applicable 
for 

–TH (theatre) version (refer to spacing tables for installation positions): 

 

 

 

Refer to the Technical Label for classification information.

 

Caution:

 

On many building sites, power circuits may be cut off in an uncontrolled and repetitive basis during 
construction. As a result, any Exit & Emergency Units, on these circuits, will have their batteries 
discharged or “cycled”. The battery in this fitting has been selected to give excellent long-life 
performance in a controlled AS2293 testing environment. Excessive battery cycling will reduce through-
life performance and may lead to premature battery failure. Battery warranty claims, as a result of such 
abuse, are specifically EXCLUDED from Clevertronics warranty terms. 

Warranty:

 

For Product Warranty information and Terms and Conditions of Sales please refer to our website 

http://clevertronics.com.au/terms-conditions-sale-australia-nz/

 

 

 

Отзывы: