1943075
V2.6
March 2019
Testing:
Once connected to the 240V mains supply, the unit must be allowed to charge the battery for at least 24
hours. Conduct the following tests:
•
For the first test, the emergency lamp must remain illuminated for at least 2 (4 for the -4HR) hours
after disconnection from the mains supply.
•
Subsequent tests require the unit to illuminate for at least 90 minutes (4 hours for -4HR). The results
of all tests are required to be recorded in a service logbook, which is to be kept on-site at all times.
If the unit fails to remain illuminated for the requisite time, remedial action must be taken to repair
the situation and once completed, the unit must pass a subsequent test. For more specific
information, please refer to the current edition of the AS 2293.3 Standard.
Swingblade Maintenance:
Battery/Lamp Replacement:
•
Prise off the plastic end caps from ends
using a terminal screwdriver
•
Disconnect the lamp lead from the PCB
and slide out the LED light bar.
•
Reinsert new LED light bar, reconnect the
lamp lead and replace the plastic end cap..
•
Remove the central screw connecting the
two earth leads to the earth bar. This screw
holds the equipment tray in place.
•
Slide the gear tray out from the test
switch/light bar end, unplugging the AC
connector once it is revealed.
•
Unplug the battery lead then bend back the
metal tabs securing the battery pack.
Remove the battery and replace with the
changeover battery pack.
•
Re-assemble the fitting reversing the above
procedure. It is important that the screw
securing the two earth leads is re-installed
and tightened correctly.
Trouble Shooting:
Below are a list of common problems and their
possible causes.
Fault:
The Green LED Test Switch
indicator is not illuminated.
Check: A.C. is connected and is turned on.
Battery is connected
Test Switch for damage.
Fault:
Lamp does not illuminate in
emergency mode.
Check: A.C. is connected.
Lamp is correctly inserted.
Battery is connected
Fault:
Lamp illuminates in emergency
mode, but only stays on for a short
period.
Check:
Battery has been allowed to charge for
at least 24 hours.
Battery for damage.
Rated Emergency Lumen Output in accordance with AS2293.1 (refer
to spacing tables for installation positions):
Refer to tech label for classification details (Not applicable to TH version).
Caution:
On many building sites, power circuits may be cut off in an uncontrolled and repetitive basis during
construction. As a result, any Exit & Emergency Units, on these circuits, will have their batteries
discharged o
r “cycled”. The battery in this fitting has been selected to give excellent long life performance
in a controlled AS2293 testing environment. Excessive battery cycling will reduce through-life performance
and may lead to premature battery failure. Battery warranty claims, as a result of such abuse, are
specifically EXCLUDED from Clevertronics warranty terms.
Warranty:
For Product Warranty information and Terms and Conditions of Sales please refer to our website
http://clevertronics.com.au/terms-conditions-sale-australia-nz/
LP™ Swingblade LED
Installation & Maintenance Instruction Leaflet
Designed in Australia to comply with the
requirements of AS2293.3: 2005 and AS/NZS
CISPR15: 2011.
NOTE: Standard product codes with this symbol are
enabled with Clevertest Plus capability. Please refer
to the operation guide supplied with the product for
details.
Victoria (Head Office & Manufacturing)
195 Chesterville Rd Moorabbin VIC 3189
Phone:
+61 3 9559 2700
Fax:
+61 3 9559 2799
News South Wales
Phone:
+61 2 8805 6400
Fax:
+61 2 8805 6444
Queensland
Phone:
+61 7 3442 9700
Fax:
+61 7 3442 9777
South Australia/Northern Territory
Phone:
+61 8 8301 8800
Fax:
+61 8 8351 8286
Western Australia
Phone:
+61 8 9248 3720
Fax:
+61 8 9248 3725
New Zealand
Phone:
+64 800 548 448
Models:
CSBLED-yy-xx-ss-zz
CCSBLED-yy-xx-ss-zz (Classic blade option)
Testing
:
Options
:
Special Legend
ss = SP
Manual Test
xx = Blank
4 Hour runtime
zz = 4HR
Zoneworks
xx = ZW
Fire Panel Sound Control
zz = SND-24V
Zoneworks DATA
xx = DATA
Zoneworks Sound Control
zz =
SND
DALI Compatible xx = DALI
Theatre
yy = TH
Clevertest
xx = CT
(
NOTE: Products supplied with the Clevertest Plus Symbol are
activated with Clevertest PLUS capability. Please refer to the operation guide
supplied with the product for details).
Spare Parts:
1550070
BATT: LP 3.2V 3200mAh 200mm lead, sp.BRKT
1550235
BATT: LP -4HR 3.2V 6400mAh.200mm lead.Brkt
8002355
PCA: Swingblade LED Driver
8002354
PCA:LBSLED-TH #CT10164-L4 6C20 (for use with -TH options)
8002185
PCA: Swingblade Duris LED Strip
Important:
It is illegal for anyone, except for a licensed electrician to install or maintain this product. Before installation,
ensure that the electricity supply has been switched off and isolated. Installation must be carried out in
accordance with the relevant Australian and International Standards.