Testing:

 

Once connected to the 240V mains supply, the unit must be allowed to charge the battery for at least 24 
hours. Conduct the following tests: 

 

For the first test, the emergency lamp must remain illuminated for at least 2 (4 for the -4HR) hours 
after disconnection from the mains supply. 

 

Subsequent tests require the unit to illuminate for at least 90 minutes (4 hours for -4HR). The results 
of all tests are required to be recorded in a service logbook, which is to be kept on-site at all times. 
If the unit fails to remain illuminated for the requisite time, remedial action must be taken to repair 
the  situation  and  once  completed,  the  unit  must  pass  a  subsequent  test.  For  more  specific 
information, please refer to the current edition of the AS 2293.3 Standard. 
 

Swingblade Maintenance: 

 

Battery/Lamp Replacement:

 

 

Prise off the plastic end caps from ends 
using a terminal screwdriver 

 

Disconnect the lamp lead from the PCB 
and slide out the LED light bar.  

 

Reinsert new LED light bar, reconnect the 
lamp lead and replace the plastic end cap.. 

 

Remove the central screw connecting the 
two earth leads to the earth bar. This screw 
holds the equipment tray in place.  

 

Slide the gear tray out from the test 
switch/light bar end, unplugging the AC 
connector once it is revealed.  

 

Unplug the battery lead then bend back the 
metal tabs securing the battery pack. 
Remove the battery and replace with the 
changeover battery pack. 

 

Re-assemble the fitting reversing the above 
procedure. It is important that the screw 
securing the two earth leads is re-installed 
and tightened correctly. 

Trouble Shooting: 

Below are a list of common problems and their 
possible causes. 

 
Fault:  

The Green LED Test Switch 
indicator is not illuminated.

 

Check:   A.C. is connected and is turned on. 
 

Battery is connected 
Test Switch for damage. 
 

Fault:  

Lamp does not illuminate in 
emergency mode. 

 

Check:   A.C. is connected. 
 

Lamp is correctly inserted. 

 

Battery is connected 

 

Fault:  

Lamp illuminates in emergency 
mode, but only stays on for a short 
period. 

Check: 

Battery has been allowed to charge for 
at least 24 hours. 

 

Battery for damage.

 

 

Rated Emergency Lumen Output in accordance with AS2293.1 (refer 
to spacing tables for installation positions):

 

Refer to tech label for classification details (Not applicable to TH version). 

 

Caution:

 

On  many  building  sites,  power  circuits  may  be  cut  off  in  an  uncontrolled  and  repetitive  basis  during 
construction.  As  a  result,  any  Exit  &  Emergency  Units,  on  these  circuits,  will  have  their  batteries 
discharged o

r “cycled”. The battery in this fitting has been selected to give excellent long life performance 

in a controlled AS2293 testing environment. Excessive battery cycling will reduce through-life performance 
and  may  lead  to  premature  battery  failure.  Battery  warranty  claims,  as  a  result  of  such  abuse,  are 
specifically EXCLUDED from Clevertronics warranty terms. 
 

Warranty:

 

 
For Product Warranty information and Terms and Conditions of Sales please refer to our website 

http://clevertronics.com.au/terms-conditions-sale-australia-nz/

 

 
 
 

 
 
 

 

 

LP™ Swingblade LED 

 

Installation & Maintenance Instruction Leaflet

 

 

Designed in Australia to comply with the 
requirements of AS2293.3: 2005 and AS/NZS 
CISPR15: 2011. 
 

NOTE: Standard product codes with this symbol    are 
enabled with Clevertest Plus capability.  Please refer 
to the operation guide supplied with the product for 
details.

 

Victoria (Head Office & Manufacturing) 

195 Chesterville Rd Moorabbin VIC 3189  

Phone:

 +61 3 9559 2700  

Fax:

 +61 3 9559 2799 

News South Wales

 

Phone: 

+61 2 8805 6400

 

Fax:    

+61 2 8805 6444

 

Queensland

  

Phone:

  +61 7  3442 9700 

Fax:

     +61 7  3442 9777 

South Australia/Northern Territory

  

Phone:

 +61 8 8301 8800 

Fax:

   +61 8 8351 8286 

Western Australia

  

Phone:

 +61 8 9248 3720 

Fax:

   +61 8 9248 3725 

New Zealand 
Phone: 

+64 800 548 448 

 

Models:  

 

CSBLED-yy-xx-ss-zz  
CCSBLED-yy-xx-ss-zz  (Classic blade option) 

Testing

 

:

 

 

 

Options

:

 

Special Legend

 

ss = SP 

 

Manual Test  

xx = Blank 

 

4 Hour runtime 

zz = 4HR

 

 

Zoneworks 

xx = ZW 

 

Fire Panel Sound Control

 

zz = SND-24V

 

 

Zoneworks DATA   

xx = DATA 

 

Zoneworks Sound Control

 

zz =

 

SND

 

 

DALI Compatible       xx = DALI 

 

Theatre 

yy = TH 

 

Clevertest 

xx = CT 

 (

NOTE: Products supplied with the Clevertest Plus Symbol     are 

activated with Clevertest PLUS capability. Please refer to the operation guide 

supplied with the product for details). 

Spare Parts:  

1550070 

BATT: LP 3.2V 3200mAh 200mm lead, sp.BRKT

 

1550235

 

BATT: LP -4HR 3.2V 6400mAh.200mm lead.Brkt

 

8002355

 

PCA: Swingblade LED Driver

 

8002354 

PCA:LBSLED-TH #CT10164-L4 6C20 (for use with -TH options) 

8002185

 

PCA: Swingblade Duris LED Strip

 

 

Important:

 

 

It is illegal for anyone, except for a licensed electrician to install or maintain this product. Before installation, 
ensure that the electricity supply has been switched off and isolated. Installation must be carried out in 