1942498
V1.2
20 May 2022
Installation:
The Circular can be installed in either a ceiling mounted or wall mounted configuration.
•
Remove the diffuser by rotating it counter-clockwise.
•
Remove the gear-tray by loosening the 3 screws holding it in place and then slightly rotating the
gear-tray clockwise to release it from the keyhole slots.
•
The power cable entry to the luminaire is via the rear surface of the base through the existing
20mm hole. Ensure appropriate cable entry provisions are made on the installation surface for this
purpose.
•
The base of the luminaire can be mounted to the installation surface with the use of suitable
fasteners (Not provided). These fasteners should be placed through the mounting feet of the base
of the luminaire.
•
Route the power cable into the base via the existing 20mm hole at the rear of the base during the
installation of the base.
•
Secure the gear-tray to the base by connecting the lanyard extending from the base to the gear-
tray.
•
Connect the 240VAC (N, A
EM
, A
SW
, Earth) supply to the terminal block of the gear tray. (For DALI or
DATA luminaires, terminate the additional wires to the appropriately marked terminals.)
•
Secure the gear-tray to the base via the keyhole slots on the gear-tray and by tightening the 3
screws.
•
Fit the diffuser to the base by placing the diffuser over the base and then rotating it clockwise,
ensuring all the slide-lock points are engaged.
•
Apply power to the luminaire and test as per the instructions.
•
If the CTP capabilities are activated, please affix the CTP status label to a visible surface and
update the Four Segment Marking on the product to include a ‘’F’’ in third segment block.
Dimensions:
Complete luminaire outer dimensions:
327mm (Diameter) x 100mm (Max Height)
Base Diameter:
272mm
Rated Emergency Lumen Output in accordance with AS/NZS 2293.1 (refer to spacing
tables for installation positions):
Refer to the Technical Label for classification information.
Warranty:
For Product Warranty information and Terms and Conditions of Sales please refer to our website
http://clevertronics.com.au/terms-conditions-sale-australia-nz/
Testing:
Once connected to the 240V mains supply, the luminaire must be allowed to charge the battery for at
least 24 hours. Conduct the following tests:
•
For the first test, the emergency lamp must remain illuminated for at least 2 hours (4 hours for -
4HR luminaires) after disconnection from the mains supply.
•
Subsequent tests require the luminaire to illuminate for at least 90 minutes. The results of all tests
are required to be recorded in a service logbook, which is to be kept on-site at all times. If the
luminaire fails to remain illuminated for the requisite time, remedial action must be taken to repair
the situation and once completed, the luminaire must pass a subsequent test. For more specific
information, please refer to the current edition of the AS/NZS 2293.3 Standard.
Maintenance
Use only the Lamp or Battery recommended on the technical label inside the Circular.
Prior to any work, isolate the power to the luminaire that requires Lamp or Battery replacement.
Lamp Replacement:
•
Remove the diffuser by rotating it counter-clockwise to access the lamp module. If the battery
continues to power the LED Module, then remove the gear-tray by loosening the 3 screws holding
it in place and then slightly rotating the gear-tray clockwise to release it from the keyhole slots.
Disconnect the battery connector from the Emergency Driver. Then refit the gear-tray to the base.
•
Gently push into the top of the wiring terminals and pull out the wires from the LED Module.
•
Un-do the 4 Philips head screws to disengage the LED module from the gear-tray.
•
Fit the new LED Module to the gear-tray by following the above process in reverse. Ensure the
battery connector is refitted, if it was removed during the lamp replacement process.
Maintenance - Battery Replacement:
•
Obtain access to the rear side of the gear-tray by removing the diffuser by rotating it counter-
clockwise; Then remove the gear-tray by loosening the 3 screws holding it in place and then slightly
rotating the gear-tray clockwise to release it from the keyhole slots.
•
Disconnect the battery connector from the Emergency Driver.
•
Un-do the 2 Philips head screws to remove the battery and then replace it with the new battery,
ensuring that the tooth-washers are re-used.
•
Fit the battery connector to the Emergency Driver.
•
Refit the gear-tray and diffuser by following the above process in reverse.
Trouble Shooting:
Below are a list of common problems and their possible causes.
Fault: The Green LED Test Switch indicator is not illuminated.
Check: A.C. is connected and is turned on.
Battery is connected
Test Switch for damage.
Fault: Lamp does not illuminate in emergency mode.
Check: A.C. is connected.
Lamp is correctly inserted.
Battery is connected
Fault: Lamp illuminates in emergency mode, but only stays on for a short period.
Check: Battery has been allowed to charge for at least 24 hours.
Battery for damage.
Caution:
On many building sites, power circuits may be cut off in an uncontrolled and repetitive basis during
construction. As a result, any Exit & Emergency Luminaires on these circuits will have their batteries
discharged or “cycled”. The battery in this luminaire has been selected to give excellent long-life
performance in a controlled AS/NZS 2293.1 testing environment. Excessive battery cycling will reduce
through-life performance and may lead to premature battery failure. Battery warranty claims, as a result
of such abuse are specifically EXCLUDED from Clevertronics warranty terms.