Installation:

 

The  L10  Weatherproof  (WP)  LED  Exit  is  a  2-part  assembly.  The  LED  light  source  and  EXIT  decal  is 
housed in a separate WP enclosure to the WP control gear enclosure. The EXIT enclosure is suitable for 
temperature  environments  of  -40°C  to  +40°C.    The  remote-control  gear  enclosure  is  suitable  for 
temperatures of 0°C to +40°C. The enclosure bases are attached to the wall using screws installed through 
the 4 isolated holes. The remote-control gear enclosure is connected to the EXIT enclosure via a 2-core 
cable to be supplied by the installer (not supplied by Clevertronics with the product). To install the 2-part 
assembly follow these steps.   

Remote Control Gear 

1. 

Remove the enclosure cover (4 plastic screws at each corner).  

2. 

Remove the gear tray (4 screws holding the gear tray onto 4 mounting posts). 

3. 

Determine power entry hole (typically the back) and separately the hole for the 2-core cable 
(end/side) to the EXIT enclosure. 

4. 

Drill power access hole in the box base and separately the hole for the 2-core cable to the EXIT 
enclosure. 

5. 

Position the box base in the mounting position.  

6. 

Mark the 4 holes for mounting. Install the base using appropriate fixings (not supplied). 

7. 

Connect the 240VAC supply to the terminal block labelled L, N, E.  

8. 

Reinstall the gear tray and reinstall the enclosure cover. 

EXIT Enclosure 

9. 

Please refer to 1947440 Weatherproof LED Exit Enclosure for installation instructions.  

2 core cable connection between the 2 enclosures 

10.  During the installation of each component the installer should consider installing the 

interconnecting cable between the two components.  This will avoid the need to re-visit each 
enclosure and opening the covers and remove the gear trays a second time.  

11.  The 2-core interconnecting cable should use a conductor size of 1.5mm

2

 to a maximum distance of 

2m. For lengths greater than 2m, a 2.5mm

2

 conductor should be used and the cable should be fire 

rated to class WS4X up to a distance of 10m.  Please contact Clevertronics for advice on cable 
lengths and cable size beyond 10m.   

12.  Terminate the cable at each end (each enclosure) to the appropriate terminations in the images 

below marked LED+ and LED-.   

NOTE: ensure that any cable entry point is suitably sealed using a gland appropriate to the cable type 
and size or the entry hole is sealed using a suitable compound such as silicone.  

 

If the CTP capabilities are activated, please affix the CTP status Label to a visible surface and Four 
Segment Marking on the product w

ill include an ‘’F’’ in third segment block.  

 
Networking: 

When installing the product on a monitored network, (ZONEWORKS, DATA, DALI) simply insert the 
relevant Smart Node PCA. 

Dimensions: 

 

Testing:

 

Once connected to the 240V mains supply, the unit must be allowed to charge the battery for at least 24 
hours. Conduct the following tests: 

 

For the first test, the emergency lamp must remain illuminated for at least 2 hours (4 hrs for the -
4HR fittings) after disconnection from the mains supply. 

 

Subsequent tests require the unit to illuminate for at least 90 minutes. The results of all tests are 
required to be recorded in a service logbook, which is to be kept on-site at all times. If the unit fails 
to remain illuminated for the requisite time, remedial action must be taken to repair the situation 
and once completed, the unit must pass a subsequent test. For more specific information, please 
refer to the current edition of the AS 2293.3 Standard. 

 

Maintenance: 

 

Lamp Replacement:

 

 

Use only the lamp(s) recommended on the 
label inside the Weatherproof Exit.  

 

To replace the lamp bar, remove the screws, 
disconnect the signal cable and install the 
new lamp bar. 

 

Battery Replacement:

 

 

Use only the battery recommended on the 
label inside the Exit fitting and on this 
instruction. 

 

Remove the cable ties holding the battery, 
un-plug the lead from the PCB and remove 
the old battery.  

 

Clip the new battery into the holder, route the 
DC cable to the PCB and plug the new 
battery into the PCB.  

 

Secure the battery using suitable cable ties 

Trouble Shooting: 

Below are a list of common problems and their 
possible causes. 

 
Fault:  

The Green LED Test Switch indicator 
is not illuminated.

 

Check:   A.C. is connected and is turned on. 
 

Battery is connected. 
Test Switch for damage. 
 

Fault:  

Lamp does not illuminate in 
emergency mode. 

 

Check:   A.C. is connected. 
 

Lamp is correctly inserted. 

 

Battery is connected 

 

Fault:  

Lamp illuminates in emergency 
mode, but only stays on for a short 
period. 

Check: 

Battery has been allowed to charge for 
at least 24 hours. 

 

Battery for damage.

 

 
Rated Emergency Lumen Output in accordance with AS2293.1, not applicable 
for 

–TH (theatre) version (refer to spacing tables for installation positions): 

 

 

 

Refer to the Technical Label for classification information.

 

Caution:

 

On many building sites, power circuits may be cut off in an uncontrolled and repetitive basis during 
construction. As a result, any Exit & Emergency Units, on these circuits, will have their batteries 
discharged or “cycled”. The battery in this fitting has been selected to give excellent long-life 
performance in a controlled AS2293 testing environment. Excessive battery cycling will reduce through-
life performance and may lead to premature battery failure. Battery warranty claims, as a result of such 
abuse, are specifically EXCLUDED from Clevertronics warranty terms. 

Warranty:

 

For Product Warranty information and Terms and Conditions of Sales please refer to our website 

http://clevertronics.com.au/terms-conditions-sale-australia-nz/

 

 

 