1948806 V1.0
25 October 2018
Clevertronics Clevertest and Clevertest Plus
Refer to the supplementary operation guide supplied with the Product.
After Power ON, the Status LED on a Clevertest Plus enabled fitting will display a rapid Green or Red
flashing for a period up to 2 minutes.
The diffuser will require removal to gain access to the Test/Status Switch and LED.
Maintained fittings (LVP2LED
M
-P-xx-yy) cannot be scanned with a camera using the CleverSparky App
as the maintained light source interferes with the camera scanning function. To register the fitting
manually enter the serial number from the QR code and visually read the test result and enter manually
into CleverSparky.
Zoneworks and DATA Monitored Options
Battens with part numbers including -ZW
, -DATA
are fitted with Zoneworks communications modules
(nodes).These battens are monitored using either Powerline Carrier Technology that utilises the power
cable to provide data communication or a dedicated data cable to/from data routers installed on a
dedicated data trunk connected to a central Server (can also be connected via Ethernet/Internet/Fibre).
Zoneworks software on the server is used to monitor, coordinate testing and collate test data from each
batten and can be commissioned by scanning of the supplied barcode. The LED Test Switch indicator
provides a multifunction indication of the status of the batten during testing and normal operation:
State
LED Operation
Commissioned
LED on Solid (Green)
Un-commissioned
LED flashes at 0.5Hz (0.5s Green, 0.5s Yellow)
Emergency Light Test In Progress
LED flashes at 3s On (Yellow) & 0.5s Off
In the case of the DATA version a 2-
way “figure 8” cable and terminal block facilitates the connection to
the DATA network via a multi-drop bus (daisy chain connection). For further information of installation of
a Zoneworks system, please refer to the Zoneworks Users Guide and Commissioning Guide (incl. DATA
version)
DALI EM Option
Battens with part numbers including
-DALI
are fitted with DALI modules (nodes) that facilitate connection
and integration to 3
rd
Party Lighting Control Systems. Before installing the -DALI batten please confirm
that the Lighting Control System has the capability to monitor DALI Emergency Luminaires. The -DALI
batten will be addressed and configured into the control system by the Lighting Control System
Commissioning Technicians and not Clevertronics.
State
LED Operation
Commissioned/ Un-commissioned
LED on Solid (Green)
Emergency Light Test in progress
LED flashes at 1s On (Yellow) & 1s Off
“IDENTIFY COMMAND”
Fitting goes into emergency mode for 10 seconds
A 2-
way “figure 8” cable and terminal block facilitates the connection to the DALI network. DALI
connections are marked as Da Da.
L10™ 2ft LED Weatherproof Vandal Resistant Batten
Installation & Maintenance Instruction Leaflet
Victoria (Head Office & Manufacturing)
195 Chesterville Rd
Moorabbin VIC 3189
Phone:
+61 3 9559 2700
Fax:
+61 3 9559 2799
New South Wales
Phone:
+61 2 8805 6400
Fax:
+61 2 8805 6444
Queensland
Phone:
+61 7 3442 9700
Fax:
+61 7 3442 9777
South Australia/Northern Territory
Phone:
+61 8 8301 8800
Fax:
+61 8 8351 8286
Western Australia
Phone:
+61 8 9248 3720
Fax:
+61 8 9248 3725
New Zealand
Phone: +64 800 548 448
Designed in Australia to comply with the requirements of
AS2293.3: 2005 and AS/NZS CISPR15: 2011
NOTE: Standard product codes with this symbol are
enabled with Clevertest Plus capability. Please refer to the
operation guide supplied with the product for details.
Models:
LVP2LEDM-P-xx-yy
Testing :
Options:
Manual Test
xx = Blank
4HR Battery
yy=4HR
Zoneworks
xx = ZW
Z/W DATA
xx = DATA
DALI Comp.
xx = DALI
Clevertest
xx = CT
(NOTE: -CT Products supplied with the Clevertest Plus Symbol are activated with
Clevertest PLUS capability. Please refer to the operation guide supplied with the product for
details).
Spare Parts:
1330055
LED Driver - LC 50w 350-1050mA, 20-50V
LCPLED-38V120C-CKIT
LED Power Pack,38V 120mA,L10
1530260
BATT:L10 6.6V 2500mAh.200mm lead.SBS.
8002699
PCA:LED Strip 5P8S, ALS-50-840-3-01-C
Important:
It is illegal for anyone, except for a licensed electrician to install or maintain this product. Before installation,
ensure that the electricity supply has been switched off and isolated. Installation must be carried out in
accordance with the relevant Australian and International Standards.