Testing:
Once connected to the 240V mains supply, the unit must be allowed to charge the battery for at least 24
hours. Conduct the following tests:
•
For the first test, the emergency lamp must remain illuminated for at least 2 hours after disconnection
from the mains supply.
•
Subsequent tests require the unit to illuminate for at least 90 minutes. The results of all tests are
required to be recorded in a service logbook, which is to be kept on-site at all times. If the unit fails
to remain illuminated for the requisite time, remedial action must be taken to repair the situation and
once completed, the unit must pass a subsequent test. For more specific information, please refer
to the current edition of the AS 2293.3 Standard.
LED Exit Maintenance:
Lamp Replacement:
•
Use only the LED lamp strip recommended
on the label inside the Exit fitting or this
instruction.
•
To replace the lamp, loosen the cover
screws and remove, unplug lamp
connector, remove nuts fastening lamp strip
and remove, replace and reassemble.
Battery Replacement:
•
Use only the battery recommended on the
label inside the Exit fitting and on this
instruction.
•
Un-plug the lead from the Inverter pack.
Remove the old battery and install the new
one.
•
Reconnect the battery cable to the inverter
pack.
Trouble Shooting:
Below are a list of common problems and their
possible causes.
Fault:
The Green LED Test Switch
indicator is not illuminated.
Check: A.C. is connected and is turned on.
Battery is connected
Test Switch for damage.
Fault:
Lamp does not illuminate in
emergency mode.
Check: A.C. is connected.
Lamp is correctly inserted.
Battery is connected
Fault:
Lamp illuminates in emergency
mode, but only stays on for a short
period.
Check:
Battery has been allowed to charge for
at least 24 hours.
Battery for damage.
Rated Emergency Lumen Output in accordance with AS2293.1 (refer to
spacing tables for installation positions):
C0=D6.3 C90=E3.2
Caution:
On many building sites, power circuits may be cut off in an uncontrolled and repetitive basis during
construction. As a result, any Exit & Emergency Units, on these circuits, will have their batteries
discharged or “cycled”. The battery in this fitting has been selected to give excellent long life performance
in a controlled AS2293 testing environment. Excessive battery cycling will reduce through-life performance
and may lead to premature battery failure. Battery warranty claims, as a result of such abuse, are
specifically EXCLUDED from Clevertronics warranty terms.
Warranty:
For Product Warranty information and Terms and Conditions of Sales please refer to our website
http://clevertronics.com.au/terms-conditions-sale-australia-nz/
L10™ Jumbo LED Exit
Installation & Maintenance Instruction Leaflet
Designed in Australia to comply with the
requirements of AS2293.3: 2005 and AS/NZS
CISPR15: 2011.
NOTE: Standard product codes with this symbol are
enabled with Clevertest Plus capability. Please refer to
the operation guide supplied with the product for details.
Victoria (Head Office & Manufacturing)
195 Chesterville Rd
Moorabbin VIC 3189
Phone: +61 3 9559 2700
Fax: +61 3 9559 2799
News South Wales
Phone: +61 2 8805 6400
Fax: +61 2 8805 6444
Queensland
Phone: +61 7 3442 9700
Fax: +61 7 3442 9777
South Australia/Northern Territory
Phone: +61 8 8301 8800
Fax: +61 8 8351 8286
Western Australia
Phone: +61 8 9248 3720
Fax: +61 8 9248 3725
New Zealand
Phone: +64 800 548 448
Models:
LJELED-40-xx
Testing
:
Manual Test
xx = Blank
Zoneworks
xx = ZW
Zoneworks DATA xx = DATA
DALI Compatible
xx = DALI
Clevertest
xx = CT
(
NOTE:-CT Products supplied with the Clevertest Plus Symbol are
activated with Clevertest PLUS capability. Please refer to the operation
guide supplied with the product for details).
Spare Parts:
1530010
BATTERY:L10 3.3V 2.5AH. 200mm lead.Brkt
8002470
PCA: Duris E5 Strip for LJELED.CT10050-D1
LJELED-40-CKIT-110
Jumbo LED Exit, Control Kit, L10
Important:
It is illegal for anyone, except for a licensed electrician to install or maintain this product. Before installation,
ensure that the electricity supply has been switched off and isolated. Installation must be carried out in
accordance with the relevant Australian and International Standards.