1942032
V1.1
3 March 2020
Testing:
When the LLIFE-PRO-SPOT unit is connected to the un-switched active, it must be allowed to charge the
battery for at least 24 hours. The emergency lamp only illuminates during a power fail. Conduct the
following tests:
•
The emergency lamp must illuminate for at least 2 hours after disconnection from the mains. The
results of all tests are required to be recorded in a service logbook, which is to be kept on-site at all
times. If the unit fails to illuminate for the requisite time, remedial action must be taken to repair the
situation and once completed, the unit must pass a subsequent test.
•
Press and hold Test Button or switch Off Mains Supply, check that the emergency lamp is On.
•
Release the Test Button or Switch On Mains Supply, check that the emergency lamp is Off
(Non-maintained operation).
Below are a list of common problems and their possible causes:
Fault: The Green LED indicator is not illuminated.
Check: A.C. is connected and is turned on.
Battery is connected.
Test Switch for damage.
Fault: Lamp does not illuminate in emergency mode.
Check: A.C. is connected.
Lamp is correctly inserted.
Battery is connected
Fault: Lamp illuminates in emergency mode, but only stays on for a short period.
Check: Battery has been allowed to charge for at least 24 hours.
Battery for damage.
Rated Emergency Lumen Output in accordance with AS2293.1 (refer to
spacing tables for installation positions):
N/A
Caution:
On many building sites, power circuits may be cut off in an uncontrolled and repetitive basis during
construction. As a result, any Lifelight Units, on these circuits, will have their batteries discharged or
“cycled”. The Li-ion battery in the Lifelight has been selected to give excellent long life performance in a
controlled IEC 60598-2-22 testing environment. Excessive battery cycling will reduce through-life
performance and may lead to premature battery failure. Battery warranty claims, as a result of such
abuse, are specifically EXCLUDED from Clevertronics warranty terms.
Warranty:
For Product Warranty information and Terms and Conditions of Sales please refer to our website
http://clevertronics.com.au/terms-conditions-sale-australia-nz/
Installation:
This LLIFE-PRO-SPOT Surface Mount Non-maintained Spotlight Emergency Luminaire can be
installed on any solid surface.
•
Locate the installation position.
•
Refer Images and Dimensions below for the Cut-out Hole and other dimensions.
•
Pre-drill mounting and cable access holes.
•
Route the LED cable from the head through the surface access hole.
•
Mount the LED head using suitable fixings.
•
Connect the LED cable to the control gear pack
•
Ensure the Battery is connected.
•
Apply power to the unit and test per instructions.
Upgrading a LLIFE-PRO to Clever-test, Zoneworks (incl. DATA) or
DALI EM
All LP Lifelight PRO Emergency Luminaires (LLIFE-PRO-SPOT) can be upgraded to Clever-test,
Zoneworks, Zoneworks DATA or DALI EM.
When upgrading simply insert the relevant smart node board.
Unlike previous versions of product DO NOT remove or alter the configuration of jumpers.
There is NO need to remove any jumper for the correct operation of the plugin node.
Images and Dimensions: Mounting plate