background image

1942306 

V1.4  

20 May 2022 

 

Clevertest and Clevertest Plus 

 

Refer to the supplementary operation guide supplied with the Product.

  

 

After Power ON, the Status LED on a Clevertest Plus enabled fitting will display a rapid Green or Red 

flashing for a period up to 2 minutes. 

 

Zoneworks, HIVE and DATA Monitored Options

 

Fittings with part numbers -ZW

, -HV/-HVG, -DATA 

are fitted with Zoneworks communications modules 

(nodes). These fittings are monitored using either Powerline Carrier Technology that utilize the power 

cable to provide data communication, RF transceiver modules operating in the ISM band or a dedicated 

data cable to/from data routers installed on a dedicated data trunk connected to a central Server (can 

also be connected via Ethernet/Internet/Fibre). Zoneworks software on the server is used to monitor, 

coordinate testing and collate test data from each fitting. Zoneworks Fittings can be commissioned by 

a single push of the test switch or by scanning the supplied barcode. The LED Test Switch indicator 

provides a multifunction indication of the status of the fitting during testing and normal operation: 

Option 

State 

LED Operation 

ZW, HV, HVG, 

DATA 

Commissioned 

LED on Solid (Green) 

ZW, DATA 

Un-commissioned 

Batt plugged-in:

 yellow 1s, green 1s 

Batt unplugged:

 red 1s, off 1s 

HV, HVG 

Un-commissioned 

With network connectivity 

Batt plugged-in:

 yellow 1s, green 1s 

Batt unplugged:

 red 1s, off 1s 

HV, HVG 

Un-commissioned 

Without network connectivity 

Batt plugged-in:

 yellow 250mS, 

green 250mS, yellow 250mS, green 

250mS, green 1s 

Batt unplugged:

 red 250mS, off 

250mS, red 250mS,off 250mS, off 1s 

ZW, DATA 

Emergency Light Test In 

Progress 

LED flashes at yellow 5s , 0ff 1s 

HV, HVG 

Emergency Light Test In 

Progress 

LED flashes at yellow 1s , 0ff 1s 

In the case of the DATA version a 2-way “figure 8” cable and terminal block facilitates the connection 

to the DATA network via a multi-drop bus (daisy chain connection).  For further information of 

installation of a Zoneworks system, please refer to the Zoneworks Users Guide and Commissioning 

Guide (incl. DATA version)  

 

DALI EM Option

 

Luminaires with part numbers having 

-DALI 

are fitted with DALI modules (nodes) that facilitate connection 

and integration to 3

rd

 Party Lighting Control Systems.  Before installing the -DALI luminaire, please confirm 

that the Lighting Control System has the capability to monitor DALI Emergency Luminaires.  The -DALI 

fitting  will be addressed and configured into the control system by the Lighting Control System 

Commissioning Technicians and not Clevertronics.   

State

 

LED Operation

 

Commissioned/ Un-commissioned  LED on Solid (Green) 
Emergency Light Test in progress  LED flashes at 1s On (Yellow) & 1s Off 
“IDENTIFY COMMAND” 

Lamp and Status LED Flash for 30 seconds 

 

A 2-way “figure 8” cable and terminal block facilitates the connection to the DALI network.  DALI 

connections are marked as Da Da.

 

 

 

 

 

 

L10™ LIFELIGHT PRO Surface Mount 

Emergency

 

Installation & Maintenance Instruction Leaflet

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Designed in Australia to comply with the requirements 

of AS2293.3: 2005 and AS CISPR15: 2017. 

 

NOTE: Standard product codes with this symbol       are 

enabled with Clevertest Plus capability.  Please refer to the 

operation guide supplied with the product for details.

 

Victoria (Head Office & Manufacturing) 

Website: 

www.clevertronics.com.au

 

Email: 

[email protected]

 

Phone: +61 3 9559 2700  

Fax: +61 3 9559 2799

 

New South Wales

 

Phone:

 +61 2 8805 6400 

Fax:

 +61 2 8805 6444

 

Queensland

  

Phone:

 +61 7 3442 9700 

Fax:

 +61 7 3442 9777 

 

South Australia/Northern Territory

  

Phone:

 +61 8 8301 8800 

Fax:

 +61 8 8351 8286 

 

Western Australia

  

Phone:

 +61 8 9207 0000 

Fax:

 +61 8 9207 0088 

 

New Zealand 

Phone: 

+64 800 548 448

 

Models:  

 

LLIFE

-PRO-SMC-xx-yy 

 

Testing

:

 

 

 

Options

:

   

 

 

Manual Test  

xx = Blank 

 

Black 

yy = BLK

 

 

Zoneworks 

xx = ZW 

 

 

   

 

Zoneworks DATA    xx = DATA 

 

 

   

 

DALI Registered       xx = DALI  

 

 

 

 

HIVE 

xx = HV/HVG 

 

 

 

 

Clevertest 

xx = CT 

(

NOTE: Products supplied with the Clevertest Plus Symbol        

are activated with Clevertest PLUS capability. Please refer to the 

operation guide supplied with the product for details). 

Spare Parts:  

1530230 

Replacement Battery 

1100869 

Replacement Emergency LED 

1100872 

Replacement Emergency LED  

(-BLK) 

AUM01370210001 

Replacement Emergency Driver 

Important:

 

 

It is illegal for anyone, except for a licensed electrician to install or maintain this product. Before installation, 

ensure that the electricity supply has been switched off and isolated. Installation must be carried out in 

accordance with the relevant Australian and International Standards. 

 

 

 

 

 

 

 

Отзывы: