Installation:

 

 

This LLIFE-PRO Recessed Non-maintained Emergency can be installed on PLASTER or T-BAR 

ceilings or used to replace an existing unit. 

 

 

First plan the assembly layout ensuring the battery is kept away from any heat source. 

 

Refer Images and Dimensions below for the Cut-out Hole and other dimensions. 

 

Use the Spring Clip Mount to mount the Head to the ceiling. 

 

Please ensure the control pack and battery is suspended above the ceiling. If the control pack and 

battery are to be mounted or placed on top of the ceiling, then please ensure the ceiling is capable 

of supporting these elements and in compliance with the relevant regulations with respect to 

mounting above/on the ceiling. 

 

If the CTP capabilities are activated, please affix the CTP status label to a visible surface and Four 

Segment Marking on the product will include an ‘’F’’ in third segment block. 

 

Networking: 

When installing the product on a monitored network, (ZONEWORKS, DATA, DALI) simply insert the 

relevant Smart Node PCA. 

 

Images and Dimensions: 

 

SQUARE HEAD 

 

Head depth: 

40mm including connector  

Head: 

60mm x 60mm  

Control gear: 

232mm (L) x 40mm (W) x 40mm (H)

 

 

ROUND HEAD 

Head depth:

 40mm including connector 

Head Diameter: 

60mm diameter (with adaptor ring 95mm) 

Cut-out Hole:

 51mm diameter (with adaptor ring up to85mm) 

Control gear:

 232mm (L) x 40mm (W) x 40mm (H) 

Battery pack:

 160mm (L) x 47mm (W) x 25mm (H), Note: 4HR version 200mm(L) x 60mm(W) x 

25mm(H).  

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Testing:

 

 

When the LLIFE-PRO unit is connected to the un-switched active, it must be allowed to charge the 

battery for at least 24 hours. The emergency lamp only illuminates during a power fail. Conduct the 

following tests: 

 

 

The emergency lamp must illuminate for at least 2 hours after disconnection from the mains. The 

results of all tests are required to be recorded in a service logbook, which is to be kept on-site at all 

times. If the unit fails to illuminate for the requisite time, remedial action must be taken to repair the 

situation and once completed, the unit must pass a subsequent test.  

 

 

Press and hold Test Button or switch Off Mains Supply, check that the emergency lamp is On. 

 

 

Release the Test Button or Switch On Mains Supply, check that the emergency lamp is Off (Non-

maintained operation). 

 

Below are a list of common problems and their possible causes: 

 

Fault:   The Green LED indicator is not illuminated.

 

Check:   A.C. is connected and is turned on. 

 

Battery is connected. 

Test Switch for damage. 

 

Fault:   Lamp does not illuminate in emergency mode. 

 

Check:   A.C. is connected. 

 

Lamp is correctly inserted. 

 

Battery is connected 

 

Fault:   Lamp illuminates in emergency mode, but only stays on for a short period. 

Check:  Battery has been allowed to charge for at least 24 hours. 

 

Battery for damage. 

 

Rated Emergency Lumen Output in accordance with AS2293.1 (refer 

to spacing tables for installation positions):

 

 

 

For emergency classification refer to product technical label. 

 

Caution:

 

 

On many building sites, power circuits may be cut off in an uncontrolled and repetitive basis during 

construction. As a result, any Lifelight Units, on these circuits, will have their batteries discharged or 

“cycled”. The Li-ion battery in the Lifelight has been selected to give excellent long-life performance in a 

controlled IEC 60598-2-22 testing environment. Excessive battery cycling will reduce through-life 

performance and may lead to premature battery failure. Battery warranty claims, as a result of such 

abuse, are specifically EXCLUDED from Clevertronics warranty terms. 

 

Warranty:

 

 

For Product Warranty information and Terms and Conditions of Sales please refer to our website 

http://clevertronics.com.au/terms-conditions-sale-australia-nz/

 

 

LED Head with Adapter Ring 

Отзывы: