Installation:

 

The LP Cleverfit Pro Dynamic Red can be installed either Ceiling or Wall Mounted. The LP Cleverfit Pro 

Dynamic Red uses a “slide connect bracket base” that is mounted and wired into position first. The main 

body can be installed once the base is wired or later to avoid damage during the construction phase. 

Please follow the steps below to install the LP Cleverfit Pro Dynamic Red Exit: 

 

Disengage the slide connect bracket from the exit body. Position the base in the mounting position.  

 

Using the bracket as a guide, mark 2 holes for mounting and one for mains access. Then install the 

bracket using appropriate fixings (not supplied). 

 

Remove the Terminal Block Cover. 

 

Route the AC power and 24/VF control cables through the access hole and connect to the terminal 

block as shown below. 

 

Connect positive signal of RED activation to I2 and negative signal to C (Common). 

 

Connect positive signal of GREEN activation to I1 and negative signal to C (Common). 

 

Reinstall the terminal block cover, Install the exit fitting to the slide bracket. 

 

To disable the Dynamic Green mode coming on in Emergency mode Set dipswitch 8 to OFF 

position. 

 

NOTE:

 Only to be used with the CleverEVAC Dynamic Red Bracket, do not use on similar brackets such 

as Cleverfit PRO(CCFPRO/LCFPRO). 

 

NOTE: For the Dip Switch setting to take effect the power and battery will need to be 

disconnected and reconnected. 

Dynamic Red 24 Volt (24V)/Volt Free (VF) Operation and Testing

 

Activation of the Dynamic Red/Green is controlled via 24V/VF control interface. The fitting comes pre-set 

as normally OFF. This is switched via an intelligent circuit inside the fitting. This is controlled by the 

24V/VF input from a fire panel or other source. If you would like to change the activation of the Dynamic 

Red/Green from Normally OFF to Normally ON change the Dip Switch no.6 (GREEN)/ no.7 (RED) on 

the Main LED Board (found under the Running Man diffuser) to 0. 

 

Selecting the Type of the Interface  

The fitting comes pre-set to the Volt Free (VF) control interface, to change this to 24V you will have to 

change the jumper on J1 from 1-2 (Image below) to 2-3 on the Contact board found next to battery 

compartment. Please see image below. 

 

Zoneworks, HIVE (HV/HVG) and DATA Monitored Options

 

Fittings with part numbers -ZW

, -HV, -HVG, -DATA 

are fitted with Zoneworks communications modules 

(nodes). These fittings are monitored using either Powerline Carrier Technology that utilize the power 

cable to provide data communication, RF transceiver modules operating in the ISM band or a dedicated 

data cable to/from data routers installed on a dedicated data trunk connected to a central Server (can also 

be connected via Ethernet/Internet/Fibre). Zoneworks software on the server is used to monitor, 

coordinate testing and collate test data from each fitting. Zoneworks Fittings can be commissioned by a 

single push of the test switch or by scanning the supplied barcode. The LED Test Switch indicator provides 

a multifunction indication of the status of the fitting during testing and normal operation: 

Option 

State 

LED Operation 

ZW, HV, HVG, 

DATA 

Commissioned 

LED on Solid (Green) 

ZW, DATA 

Un-commissioned 

Batt plugged-in:

 yellow 1s, green 1s 

Batt unplugged:

 red 1s, off 1s 

HV, HVG 

Un-commissioned 

With network connectivity 

Batt plugged-in:

 yellow 1s, green 1s 

Batt unplugged:

 red 1s, off 1s 

HV, HVG 

Un-commissioned 

Without network connectivity 

Batt plugged-in:

 yellow 250mS, green 

250mS, yellow 250mS, green 250mS, 

green 1s 

Batt unplugged:

 red 250mS, off 

250mS, red 250mS,off 250mS, off 1s 

ZW, DATA 

Emergency Light Test In Progress 

LED flashes at yellow 5s , 0ff 1s 

HV, HVG 

Emergency Light Test In Progress 

LED flashes at yellow 1s , 0ff 1s 

 

In the case of the DATA version a 2-way “figure 8” cable and terminal block facilitates the connection to 

the DATA network via a multi-drop bus (daisy chain connection).  For further information of installation of 

a Zoneworks system, please refer to the Zoneworks Users Guide and Commissioning Guide (incl. DATA 

version)  

Caution:

 

On many building sites, power circuits may be cut off in an uncontrolled and repetitive basis during construction. As a 

result, any Exit & Emergency Units, on these circuits, will have their batteries discharged or “cycled”. The battery in this 

fitting has been selected to give excellent long-life performance in a controlled AS2293 testing environment. Excessive 

battery cycling will reduce through-life performance and may lead to premature battery failure. Battery warranty claims, 

as a result of such abuse, are specifically EXCLUDED from Clevertronics warranty terms.

 

 